{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EP3600-8DS00","brand":"Siemens","brandSlug":"siemens","productSlug":"4EP3600-8DS00","canonicalUrl":"https://aoctrl.com/siemens/4EP3600-8DS00","factsUrl":"https://aoctrl.com/api/mcp/products/4EP3600-8DS00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 4EP3600-8DS00 commutating choke for converter, 3-phase, 400V AC, 16.2A rated, 18A max, 1.6mH, IP00, screw terminals.","salesMarkdown":"The Siemens 4EP3600-8DS00 is a three-phase commutating choke for converter front-end duty. It limits current rise rates and reduces harmonic distortion. Rated for 400 V AC at 50 Hz, it carries 16.2 A continuous with 18 A maximum. The 16.2 A rated current (18 A maximum) at 400 V AC three-phase sets the continuous load this choke can handle without exceeding its thermal class B (130 °C) insulation system. The 39 W coil loss and 9.1 W iron core loss total about 48 W of heat that must be dissipated into the enclosure — IP00 means no enclosure of its own, so it relies on the panel's airflow. The DC rated value of 22 A indicates the choke can handle a higher DC-side current, which matters if the converter's DC-link current exceeds the AC line rating — for example, in a regenerative drive or one with a high crest factor. The 4EP3600-8DS00 measures 0.148 m wide by 0.139 m tall by 0.078 m deep. The 3-phase design with a common core means all three lines share the same magnetic path; verify that the panel's phase-to-phase and phase-to-ground clearances meet the 400 V AC working voltage.","metaTitle":"Siemens 4EP3600-8DS00 Commutating Choke, 16.2A, 400V, 3-Phas","metaDescription":"Siemens 4EP3600-8DS00 commutating choke for converter duty. 3-phase, 400V AC, 16.2A rated, 18A max, 1.6mH, IP00. Mature lifecycle; sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.078m","Width":"0.148m","Height":"0.139m","Maximum":"18A","Rated Value":"16.2A","Phase number":"3","Type of voltage":"AC","lifecycle_stage":"mature","at DC rated value":"22A","Product designation":"Kommut.-Drossel f. Stromrichter","Protection class IP":"IP00","Inductivity rated value":"0.0016H","Power loss [W] of the coil":"39W","Operating voltage rated value":"400V","Ambient temperature rated value":"40°C","Operating frequency rated value":"50Hz","Power loss [W] of the iron core":"9.1W","Thermal class acc. to IEC 60085":"B","Type of electrical connection for main current circuit":"screw-type terminals","Relative inductive drop in voltage on the measurement level current, voltage and frequency":"4%"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=100921&mlfb=4EP3600-8DS00","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EP3600-8DS00/alternatives.json"},"ai":{"faq":[{"question":"What is 4EP3600-8DS00 used for?","answer":"It is a commutating choke (line reactor) for converter front-end duty. It limits current rise rates, reduces harmonic distortion, and protects DC-link capacitors from line notching and commutation spikes in three-phase AC drives and power converters."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EP3600-8DS00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EP3600-8DS00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}