{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EP3900-1US00","brand":"Siemens","brandSlug":"siemens","productSlug":"4EP3900-1US00","canonicalUrl":"https://aoctrl.com/siemens/4EP3900-1US00","factsUrl":"https://aoctrl.com/api/mcp/products/4EP3900-1US00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 4EP3900-1US00 mains choke (Netzdrossel f. FU), 3-phase AC, 500V rated voltage, 63A max current, 0.292mH inductance, IP00 open-frame with flat-type terminals.","salesMarkdown":"The Siemens 4EP3900-1US00 is a three-phase mains choke (line reactor) designed for installation ahead of a variable frequency drive — the German designation Netzdrossel f. FU tells you exactly that. Rated for 500 V AC at 50 Hz, it carries a maximum continuous current of 63 A and a rated operational current of 56.7 A. The 0.292 mH inductance with a 2% relative inductive voltage drop means it smooths line-side harmonics and limits inrush current without dropping excessive voltage under load. Thermal class B (130 °C rise) and 40 °C ambient rating keep it within standard panel conditions. IP00 open-frame construction means this choke is intended for enclosure mounting — it is not touch-safe on its own. Dimensions are 0.219 m wide by 0.179 m tall by 0.123 m deep, so plan for a backpanel footprint roughly 220 by 180 mm with clearance for the flat-type terminals on the main circuit connection. The 68.7 W coil losses plus 14.4 W iron core losses total about 83 W of heat to dissipate inside the cabinet; factor that into your ventilation or forced-air cooling budget.","metaTitle":"Siemens 4EP3900-1US00 Mains Choke, 3-Phase 500V 63A","metaDescription":"Siemens 4EP3900-1US00 mains choke for variable frequency drives. 3-phase, 500V AC, 63A max, 0.292mH, IP00. UL/CSA recognized. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"0.123 m","Width":"0.219 m","Height":"0.179 m","IP Rating":"IP00","Product Status":"Mature"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=490894&mlfb=4EP3900-1US00","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EP3900-1US00/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EP3900-1US00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EP3900-1US00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}