{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EP4002-6MS00","brand":"Siemens","brandSlug":"siemens","productSlug":"4EP4002-6MS00","canonicalUrl":"https://aoctrl.com/siemens/4EP4002-6MS00","factsUrl":"https://aoctrl.com/api/mcp/products/4EP4002-6MS00","rawCanonicalId":null},"summary":{"shortDescription":"SIDAC 4EP4002-6MS00, 3-phase filter reactor, 18 A rated / 20 A max, 460 V AC, 60 Hz, 5.67 % relative throttling, 12.5 kvar, IP00, screw terminals.","salesMarkdown":"The SIDAC 4EP4002-6MS00 is a 3-phase filter reactor — a line reactor — rated for 18 A continuous with a 20 A maximum, on a 460 V AC, 60 Hz system. The 0.0027 H inductance and 5.67 % relative throttling factor tell you it's sized to limit harmonic current and reduce voltage notching from a VFD or other non-linear load. The 12.5 kvar reactive power rating gives the reactive compensation capability at the fundamental frequency. The 252 Hz resonant frequency means it's tuned away from the 5th and 7th harmonics typical of 6-pulse drives, so it won't accidentally amplify those frequencies. Thermal class B (130 °C rise) per IEC 60085 keeps the copper within rating at the 40 °C ambient. The 91 W power loss at rated current needs to be factored into the panel's thermal budget.","metaTitle":"SIDAC 4EP4002-6MS00 Filter Reactor, 18A Rated, 460V AC, 3-Ph","metaDescription":"SIDAC 4EP4002-6MS00 3-phase filter reactor, 18A rated / 20A max, 460V AC, 60Hz, 5.67% throttling, 12.5 kvar, IP00. Mature lifecycle; quoted to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.143m","Width":"0.219m","Height":"0.179m","Maximum":"20A","Rated Value":"18A","Phase number":"3","Power loss [W]":"91W","Type of voltage":"AC","lifecycle_stage":"mature","Product brand name":"SIDAC","Product designation":"filter reactor","Protection class IP":"IP00","Inductivity rated value":"0.0027H","Relative throttling factor":"5.67%","Operating voltage rated value":"460V","Ambient temperature rated value":"40°C","Operating frequency rated value":"60Hz","Thermal class acc. to IEC 60085":"B","Resonant frequency of the filter":"252Hz","Reactive power of the filter bank rated value":"12 500var","Type of electrical connection for main current circuit":"screw-type terminals"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=343848&mlfb=4EP4002-6MS00","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EP4002-6MS00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 4EP4002-6MS00 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — no stock figures or prices are published here."},{"question":"What is the 4EP4002-6MS00's depth for panel layout?","answer":"The listed depth is 0.143 m. Combined with a width of 0.219 m and height of 0.179 m, it requires a clear panel footprint for mounting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EP4002-6MS00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EP4002-6MS00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}