{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU2422-0EG00-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU2422-0EG00-0AA0","canonicalUrl":"https://aoctrl.com/siemens/4EU2422-0EG00-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/4EU2422-0EG00-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 4EU2422-0EG00-0AA0 mains choke for frequency converter, 3-phase, 48 A rated current, 0.66 mH, 460 V AC, 60 Hz, IP00, Class H insulation, flat-type terminals.","salesMarkdown":"Rated 48 A continuous, with a 53 A maximum, it's sized for a drive pulling that current on a 460 V, 60 Hz three-phase system. The IP00 open-frame construction means it's intended for enclosure mounting, not standalone outdoor use — plan for a panel that keeps fingers and debris off the windings. The 48 A rated current (53 A max) is the thermal limit at 40 °C ambient with Class H insulation (180 °C rated winding hot-spot). That's a generous thermal margin — the choke can run hot without cooking the varnish, but the 40 °C ambient derating curve still applies above that. The 5% voltage drop at rated current and frequency is the impedance you're buying: it's enough to suppress harmonics and protect the drive DC bus from line notching, but low enough that you don't lose excessive voltage headroom. The 0.66 mH inductance is the value that produces that drop at 60 Hz; if your line frequency is 50 Hz, the inductive reactance drops proportionally, so the filtering effect changes — check the drive manufacturer's required minimum line impedance before committing. At 0.225 m wide, 0.21 m tall, and 0.147 m deep, this choke takes up a moderate footprint in the enclosure. IP00 means no ingress protection — mount it where no conductive dust or moisture can reach the windings, and leave at least 50 mm clearance around the core for airflow. The flat-type terminals accept crimp lugs or bus bars; torque specs per Siemens installation guidelines. Class H insulation allows a 180 °C hot-spot, so don't crowd it next to heat-sensitive electronics without a thermal barrier.","metaTitle":"Siemens 4EU2422-0EG00-0AA0 Mains Choke, 48A, 0.66mH, IP00","metaDescription":"Siemens 4EU2422-0EG00-0AA0 mains choke for VFD, 3-phase, 48A rated, 0.66mH, 460V, 60Hz, IP00, Class H. Mature lifecycle; sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.147m","Width":"0.225m","Height":"0.21m","Maximum":"53A","Rated Value":"48A","Phase number":"3","Type of voltage":"AC","lifecycle_stage":"mature","Product designation":"Netzdrossel f. FU","Protection class IP":"IP00","Inductivity rated value":"0.00066H","Operating voltage rated value":"460V","Ambient temperature rated value":"40°C","Operating frequency rated value":"60Hz","Thermal class acc. to IEC 60085":"H","Type of electrical connection for main current circuit":"flat connector","Relative inductive drop in voltage on the measurement level current, voltage and frequency":"5%"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=179178&mlfb=4EU2422-0EG00-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU2422-0EG00-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 4EU2422-0EG00-0AA0 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote — availability and current pricing are confirmed at quote time."},{"question":"What are the key specifications of 4EU2422-0EG00-0AA0?","answer":"It's a 3-phase mains choke rated 48 A (53 A max), 0.66 mH, 460 V AC, 60 Hz, with a 5% voltage drop and IP00 open-frame construction. Dimensions are 0.225 m wide, 0.21 m tall, 0.147 m deep."},{"question":"What compliance documentation is available for 4EU2422-0EG00-0AA0?","answer":"The product is designed per EN 61558-2-20 for chokes. Standard Siemens documentation includes the declaration of conformity; specific RoHS/REACH/UL status should be confirmed from the manufacturer's current compliance data sheet."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU2422-0EG00-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU2422-0EG00-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}