{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU2432-0EC00-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU2432-0EC00-0AA0","canonicalUrl":"https://aoctrl.com/siemens/4EU2432-0EC00-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/4EU2432-0EC00-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIDAC output reactor, 3-phase AC, 300 A max, 4 600 Hz rated switching frequency, IP00, flat-type terminals.","salesMarkdown":"## What this output reactor does in your drive line The Siemens SIDAC 4EU2432-0EC00-0AA0 is a 3-phase output reactor rated for a maximum continuous current of 300 A and a switching frequency of 4 600 Hz. It sits between the drive output and the motor cable, limiting the rate of voltage rise (dV/dt) and reducing capacitive charging currents in long cable runs. Connection is via flat-type terminals, so plan for busbar or lug-style wiring rather than cage clamps. The 300 A maximum current sets the motor-side thermal limit. This reactor is sized for a drive feeding a motor drawing up to that full-load current; oversizing by more than one frame risks poor high-frequency attenuation. The rated switching frequency of 4 600 Hz matches IGBT drives running at 4–6 kHz carrier — common in general-purpose VFDs. If your drive uses a lower carrier (2 kHz or below), the reactor still works but the core loss and temperature rise will be lower than the design point. The 0.012 mH inductance is a low value, typical of reactors intended for dV/dt mitigation rather than heavy harmonic filtering. Power loss splits into 110 W coil loss and 55 W iron-core loss at the rated ambient of 45 °C, thermal class H — the winding insulation handles a 180 °C hot-spot, so it can run hot in a crowded cabinet as long as airflow is not blocked. At 0.22 m wide, 0.21 m tall, and 0.13 m deep, the reactor occupies about the space of a large contactor. The flat-type terminals accept busbar or crimp lugs — not screw-clamp or spring-cage wire ends. Mount it on a flat panel or a subplate inside the cabinet; there is no DIN-rail clip. The IP00 rating means no ingress protection — keep it behind a locked door, away from dust and dripping water. Ambient temperature must not exceed 45 °C for full-rated current; derate above that per the thermal class H curve.","metaTitle":"Siemens SIDAC 4EU2432-0EC00-0AA0 Output Reactor, 300A, 4600H","metaDescription":"Siemens SIDAC 4EU2432-0EC00-0AA0 output reactor, 3-phase, 300A, 4600Hz switching frequency, IP00, flat connector terminals. Mature lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.13m","Width":"0.22m","Height":"0.21m","Maximum":"300A","Minimum":"60Hz","Rated Value":"4 600Hz","Phase number":"3","Type of voltage":"AC","lifecycle_stage":"mature","Product brand name":"SIDAC","Product designation":"output reactor","Protection class IP":"IP00","Inductivity rated value":"0.000012H","Power loss [W] of the coil":"110W","Ambient temperature rated value":"45°C","Power loss [W] of the iron core":"55W","Thermal class acc. to IEC 60085":"H","Type of electrical connection for main current circuit":"flat connector"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=285404&mlfb=4EU2432-0EC00-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU2432-0EC00-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 4EU2432-0EC00-0AA0 and what is the lead time?","answer":"This part is sourced to order through independent distribution. Availability and current pricing are confirmed at quote time against an RFQ."},{"question":"What are the key ratings for 4EU2432-0EC00-0AA0?","answer":"It is a 3-phase output reactor rated for a maximum of 300 A, a switching frequency of 4 600 Hz, and an inductance of 0.012 mH. Power loss is 110 W in the coil and 55 W in the iron core at a rated ambient of 45 °C."},{"question":"Will 4EU2432-0EC00-0AA0 drop into a panel wired for a miniature circuit breaker like 5SY6010-6KL?","answer":"No. The reactor is a power component with flat-type terminals for busbar or lug connections, while the 5SY6010-6KL is a DIN-rail mounted MCB with screw terminals. They serve different functions and have incompatible mounting and wiring."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU2432-0EC00-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU2432-0EC00-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}