{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU2532-0MD08-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU2532-0MD08-0AA0","canonicalUrl":"https://aoctrl.com/siemens/4EU2532-0MD08-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/4EU2532-0MD08-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIDAC filter reactor, 3-phase, 53.6 A rated, 220 V AC, 50 Hz, 7 % relative throttling factor, IP00, screw/flat-type terminals.","salesMarkdown":"It is rated for a 220 V AC, 50 Hz supply and carries a continuous rated current of 53.6 A, with a maximum of 59.6 A. The 53.6 A rated current (59.6 A maximum) sizes this reactor for a 220 V drive outputting roughly 18–20 kW to a motor — check your drive's continuous output current to confirm the match. The 0.58 mH inductance per phase, combined with the 7 % impedance, provides enough reactance to limit di/dt during commutation and reduce reflected wave voltage on long motor cable runs. The 189 Hz resonant frequency means this reactor self-resonates well above the 50 Hz fundamental and below typical PWM carrier frequencies (2–16 kHz), so it will not introduce a low-impedance shunt at the switching frequency. The 20 kvar reactive power rating tells you the reactive power the reactor absorbs at rated voltage — useful for power-factor correction planning if the reactor is part of a tuned filter bank. Thermal class H insulation (180 °C continuous) means the reactor can run hot without degrading the winding insulation — relevant if the panel ambient reaches 40 °C (the rated ambient) and the reactor is mounted near other heat sources. The screw-type and flat-connector terminals accept lug or busbar connections typical of panel wiring; no special crimp tool needed beyond standard hydraulic lug crimpers. At 0.225 m wide, 0.21 m tall, and 0.16 m deep, this reactor occupies roughly the footprint of a standard 9-inch by 8-inch panel area. The flat-connector and screw terminals accept busbar or cable lugs; plan for adequate clearance around the terminals for wrench access. Given class H insulation and a 40 °C ambient rating, derating is not required in a typical ventilated enclosure, but verify airflow if the panel also houses drives that dissipate several hundred watts.","metaTitle":"Siemens SIDAC 4EU2532-0MD08-0AA0 Filter Reactor, 53.6A, 220V","metaDescription":"Siemens SIDAC 4EU2532-0MD08-0AA0 3-phase filter reactor, 53.6A rated, 220V AC, 50Hz, 7% throttling, IP00. Mature lifecycle. Sourced to order. Request RFQ for pricing and availabili","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.16m","Width":"0.225m","Height":"0.21m","Maximum":"59.6A","Rated Value":"53.6A","Phase number":"3","Type of voltage":"AC","lifecycle_stage":"mature","Product brand name":"SIDAC","Product designation":"filter reactor","Protection class IP":"IP00","Inductivity rated value":"0.00058H","Relative throttling factor":"7%","Operating voltage rated value":"220V","Ambient temperature rated value":"40°C","Operating frequency rated value":"50Hz","Thermal class acc. to IEC 60085":"H","Resonant frequency of the filter":"189Hz","Reactive power of the filter bank rated value":"20 000var","Type of electrical connection for main current circuit":"flat connector / screw-type terminals"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=91313&mlfb=4EU2532-0MD08-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU2532-0MD08-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the rated current and voltage for this filter reactor?","answer":"The rated current is 53.6 A (maximum 59.6 A) on a 220 V AC, 50 Hz three-phase supply. The 7 % relative throttling factor means it drops about 7 % of line voltage at rated current."},{"question":"Where can I buy the 4EU2532-0MD08-0AA0 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — submit an RFQ for a competitive landed cost."},{"question":"What compliance documentation is available for this Siemens SIDAC reactor?","answer":"The reactor is designed to EN 61558-2-20 (safety of transformers, reactors, and power supply units). It carries a mature lifecycle status from Siemens. Specific RoHS/REACH/UL documentation should be requested at quote time, as the evidence does not list those certifications explicitly."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU2532-0MD08-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU2532-0MD08-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}