{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU2752-0EF00-4BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU2752-0EF00-4BA0","canonicalUrl":"https://aoctrl.com/siemens/4EU2752-0EF00-4BA0","factsUrl":"https://aoctrl.com/api/mcp/products/4EU2752-0EF00-4BA0","rawCanonicalId":null},"summary":{"shortDescription":"SIDAC output reactor, 3-phase AC, 80 A max, 8 kHz switching frequency, 0.1 mH, IP00, flat-type terminals.","salesMarkdown":"The SIDAC 4EU2752-0EF00-4BA0 is a 3-phase AC output reactor (output choke) rated for 80 A maximum continuous current and a switching frequency of 8 kHz. Its 0.1 mH inductance limits the rate of current rise from the drive output, protecting motor windings and cable insulation from the voltage spikes that PWM drives produce. The 160 W coil loss and 130 W iron core loss at rated load tell you the thermal load this reactor dumps into the enclosure — plan for that heat. The reactor is rated for a 40 °C ambient and carries thermal class H insulation per IEC 60085, meaning the winding can handle a 180 °C hot-spot temperature without degrading. That gives you margin if the panel runs warm or the motor cable is long. This is an IP00 open-frame reactor — no enclosure, no drip shield. It mounts inside a panel or cabinet where the ambient stays clean and dry. The main circuit terminates on flat-type connectors (bus-bar style), so you'll need a mating flat tab or a compression lug; no screw-clamp terminals here. Dimensions are 0.27 m wide by 0.24 m tall by 0.18 m deep — about the size of a small shoebox. Plan the panel layout so the reactor sits close to the drive output to keep the motor cable as short as possible on the line side.","metaTitle":"SIDAC 4EU2752-0EF00-4BA0 output reactor, 80 A, 8 kHz, IP00","metaDescription":"SIDAC 4EU2752-0EF00-4BA0 output reactor, 3-phase AC, 80 A max, 8 kHz switching, 0.1 mH, IP00, flat connectors. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.18m","Width":"0.27m","Height":"0.24m","Maximum":"80A","Minimum":"0Hz","Rated Value":"8 000Hz","Phase number":"3","Type of voltage":"AC","lifecycle_stage":"mature","Product brand name":"SIDAC","Product designation":"output reactor","Protection class IP":"IP00","Inductivity rated value":"0.0001H","Power loss [W] of the coil":"160W","Ambient temperature rated value":"40°C","Power loss [W] of the iron core":"130W","Thermal class acc. to IEC 60085":"H","Type of electrical connection for main current circuit":"flat connector"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=92919&mlfb=4EU2752-0EF00-4BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU2752-0EF00-4BA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU2752-0EF00-4BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU2752-0EF00-4BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}