{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU3022-2AA00-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU3022-2AA00-0AA0","canonicalUrl":"https://aoctrl.com/siemens/4EU3022-2AA00-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/4EU3022-2AA00-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON series commutating choke for converter, 4EU3022-2AA00-0AA0, 3-phase, 400 V AC, 50 Hz, 360 A rated / 400 A max continuous, 68 µH inductance, 4% voltage drop, IP00 open-frame, Class H insulation.","salesMarkdown":"The Siemens 4EU3022-2AA00-0AA0 is a three-phase commutating choke — a line reactor — built for converter input circuits. That 68 µH inductance (0.000068 H) and 4% relative inductive voltage drop tell you it's sized to limit current rise and smooth the DC bus ripple on a hefty drive or rectifier front end. Power loss breaks into 220 W in the coil and another 143 W in the iron core — 363 W total heat you need to vent. The Class H insulation (180 °C hot-spot) means it can run hot, but IP00 open-frame construction means it belongs inside a ventilated cabinet, not out in the washdown zone. Lifecycle stage is listed as mature — no active phase-out notice, but not a new-design recommendation either. Dimensions are 0.3 m wide, 0.269 m tall, 0.211 m deep — a sizable block, roughly the footprint of a small briefcase. Main circuit connections use flat-type terminals, so you're landing bus bars or heavy cable lugs, not wire ferrules. Plan for adequate clearance around the IP00 live parts inside the enclosure. The choke is designed per EN 61558-2-20, the standard for separating transformers and chokes for converter applications. Operating ambient temperature is rated at 40 °C; derate if your cabinet runs hotter.","metaTitle":"Siemens 4EU3022-2AA00-0AA0 Commutating Choke, 360 A, 68 µH,","metaDescription":"Siemens 4EU3022-2AA00-0AA0 commutating choke for converter, 3-phase, 400 V AC, 50 Hz, 360 A rated / 400 A max, 68 µH, 4% voltage drop, IP00, Class H. Sourced to order; RFQ for avai","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.211m","Width":"0.3m","Height":"0.269m","Maximum":"400A","Rated Value":"360A","Phase number":"3","Type of voltage":"AC","lifecycle_stage":"mature","at DC rated value":"490.1A","Product designation":"Kommut.-Drossel f. Stromrichter","Protection class IP":"IP00","Inductivity rated value":"0.000068H","Power loss [W] of the coil":"220W","Operating voltage rated value":"400V","Ambient temperature rated value":"40°C","Operating frequency rated value":"50Hz","Power loss [W] of the iron core":"143W","Thermal class acc. to IEC 60085":"H","Type of electrical connection for main current circuit":"flat connector","Relative inductive drop in voltage on the measurement level current, voltage and frequency":"4%"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=14371&mlfb=4EU3022-2AA00-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU3022-2AA00-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What are the key electrical ratings for this choke?","answer":"It's a 3-phase, 400 V AC, 50 Hz choke rated 360 A continuous (400 A max) with 68 µH inductance and a 4% relative inductive voltage drop. Power loss totals 363 W (220 W coil + 143 W core)."},{"question":"Where can I buy the 4EU3022-2AA00-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the physical size of this choke?","answer":"It measures 0.3 m wide, 0.269 m tall, and 0.211 m deep — a substantial block that needs cabinet space and ventilation."},{"question":"Will the 4EU3022-2AA00-0AA0 drop into a panel designed for a 3RV6011-0CA10 circuit breaker?","answer":"No — these are completely different component classes. The 3RV6011-0CA10 is a SIRIUS motor-protective circuit breaker (45 mm wide, DIN-rail mount). The 4EU3022-2AA00-0AA0 is a 300 mm wide chassis-mount choke with flat-type terminals. No physical or electrical interchangeability."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU3022-2AA00-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU3022-2AA00-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}