{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU3032-6MA08-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU3032-6MA08-0AA0","canonicalUrl":"https://aoctrl.com/siemens/4EU3032-6MA08-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/4EU3032-6MA08-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIDAC series, filter reactor, order code 4EU3032-6MA08-0AA0, 3-phase, 95 A rated / 105 A max, 400 V AC, 60 kvar, 0.51 mH, 5.67 % throttling, IP00.","salesMarkdown":"The Siemens SIDAC 4EU3032-6MA08-0AA0 is a 3-phase filter reactor rated 95 A continuous with a 105 A maximum, designed for 400 V AC, 50 Hz line applications. The 0.00051 H inductance at 5.67 % relative throttling factor limits harmonic distortion and reduces dv/dt stress on downstream drive components. The 60 kvar reactive power rating indicates reactive compensation capacity at rated voltage. The IP00 enclosure is an open-frame component for panel installation. ## What the thermal class and resonant frequency tell a field engineer Thermal class H per IEC 60085 means the insulation system can handle a 180 °C hot-spot temperature — this reactor can sit in a warm cabinet (40 °C ambient rated) and still carry full current without derating. The resonant frequency of 210 Hz is the point where the reactor's inductance and the system's capacitance form a parallel resonance; a field engineer checking for harmonic excitation should verify the dominant harmonics (5th at 250 Hz, 7th at 350 Hz) don't align with that 210 Hz notch. ## Termination and mounting — what you're wiring into Main circuit connections use flat connector / screw-type terminals — expect a bus-bar or ring-lug interface, not a spring-cage or pluggable connector. The footprint is 0.3 m wide by 0.269 m tall by 0.211 m deep, so plan for a panel cutout or mounting plate that accommodates those dimensions plus clearance for the terminals and airflow. IP00 means no built-in finger protection; the reactor must be mounted inside a locked or tool-accessible enclosure.","metaTitle":"Siemens SIDAC 4EU3032-6MA08-0AA0 Filter Reactor, 95A, 400V,","metaDescription":"Siemens SIDAC 4EU3032-6MA08-0AA0 filter reactor, 3-phase, 95A rated, 400V, 60 kvar, 0.51 mH, 5.67% throttling, IP00, mature lifecycle, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.211m","Width":"0.3m","Height":"0.269m","Maximum":"105A","Rated Value":"95A","Phase number":"3","Power loss [W]":"288W","Type of voltage":"AC","lifecycle_stage":"mature","Product brand name":"SIDAC","Product designation":"filter reactor","Protection class IP":"IP00","Inductivity rated value":"0.00051H","Relative throttling factor":"5.67%","Operating voltage rated value":"400V","Ambient temperature rated value":"40°C","Operating frequency rated value":"50Hz","Thermal class acc. to IEC 60085":"H","Resonant frequency of the filter":"210Hz","Reactive power of the filter bank rated value":"60 000var","Type of electrical connection for main current circuit":"flat connector / screw-type terminals"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=473016&mlfb=4EU3032-6MA08-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU3032-6MA08-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the depth and width of 4EU3032-6MA08-0AA0?","answer":"The depth is 0.211 m, the width is 0.3 m, and the height is 0.269 m. These are the overall dimensions of the open-frame reactor."},{"question":"Will this reactor drop into a panel specified around a miniature circuit breaker like 5SJ3140-7?","answer":"No — the 5SJ3140-7 is a 1-pole 40 A MCB with a 70 mm depth and DIN-rail mount. The 4EU3032-6MA08-0AA0 is a 3-phase 95 A filter reactor with screw/flat terminals and an IP00 open-frame footprint. They serve completely different functions and are not footprint-compatible."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU3032-6MA08-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU3032-6MA08-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}