{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU3622-0ES00-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU3622-0ES00-0AA0","canonicalUrl":"https://aoctrl.com/siemens/4EU3622-0ES00-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/4EU3622-0ES00-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens Netzdrossel f. FU mains choke, 4EU3622-0ES00-0AA0, 3-phase, 460V AC, 202A rated, 224A max, 60Hz, 5% voltage drop, IP00, flat-type terminals.","salesMarkdown":"## Mains Choke for Variable-Frequency Drives It's rated for 202 A continuous with a 224 A maximum, at 460 V AC and 60 Hz, with a 5% relative inductive voltage drop. The 202 A rated current (I LN) is the continuous thermal rating at 40 °C ambient — this is the number to match against your drive's input current, not the 224 A maximum (I thmax) which is a short-time overload figure. The 0.16 mH inductance at 60 Hz gives a 5% voltage drop at rated current, which is a standard value for smoothing DC-bus ripple and limiting harmonic distortion on the line side. Thermal class H (IEC 60085) means the winding insulation handles up to 180 °C hot-spot temperature — fine for a 40 °C ambient panel with some internal heat rise. The choke measures 0.35 m wide, 0.321 m tall, and 0.237 m deep. That's a substantial block — about the size of a small suitcase — so verify your panel's mounting plate has the footprint and clearance for airflow. Main circuit connections are flat-type terminals, which typically accept busbar or cable lug terminations; plan for the appropriate crimp lugs and a torque wrench. IP00 means no finger-safe enclosure, so it needs to live behind a locked panel door or inside a separate electrical room.","metaTitle":"Siemens 4EU3622-0ES00-0AA0 Mains Choke, 202A, 460V, 60Hz, IP","metaDescription":"Siemens 4EU3622-0ES00-0AA0 mains choke for frequency converters. 3-phase, 202A rated, 460V, 60Hz, 5% voltage drop, IP00. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.237m","Width":"0.35m","Height":"0.321m","Maximum":"224A","Rated Value":"202A","Phase number":"3","Type of voltage":"AC","lifecycle_stage":"mature","Product designation":"Netzdrossel f. FU","Protection class IP":"IP00","Inductivity rated value":"0.00016H","Operating voltage rated value":"460V","Ambient temperature rated value":"40°C","Operating frequency rated value":"60Hz","Thermal class acc. to IEC 60085":"H","Type of electrical connection for main current circuit":"flat connector","Relative inductive drop in voltage on the measurement level current, voltage and frequency":"5%"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=422450&mlfb=4EU3622-0ES00-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU3622-0ES00-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU3622-0ES00-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU3622-0ES00-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}