{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU3652-0AK00-1BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU3652-0AK00-1BA0","canonicalUrl":"https://aoctrl.com/siemens/4EU3652-0AK00-1BA0","factsUrl":"https://aoctrl.com/api/mcp/products/4EU3652-0AK00-1BA0","rawCanonicalId":null},"summary":{"shortDescription":"SIDAC output reactor, 3-phase AC, 94A maximum current, 0.15mH inductance, 8kHz switching frequency, IP00, flat-type terminals. Order code 4EU3652-0AK00-1BA0.","salesMarkdown":"## What this 3-phase output reactor does The SIDAC 4EU3652-0AK00-1BA0 is a 3-phase AC output reactor (choke) rated for a maximum continuous current of 94A and a switching frequency of 8kHz, with an inductance of 0.15mH. It's designed to sit between a variable-frequency drive and the motor, smoothing the PWM waveform and limiting the rate of voltage rise (dV/dt) to protect motor winding insulation. The 94A maximum current is the thermal limit under continuous duty at the rated 40°C ambient. For motor applications, this typically covers a drive rated around 75–90 kW on 400 VAC, but confirm the drive's output current against the reactor's continuous rating — the reactor must not be the bottleneck. The 8kHz switching frequency matches modern IGBT drives; if your drive runs a lower carrier frequency (2–4 kHz), the reactor still works, but core losses shift. The 0.15mH inductance provides enough impedance to limit motor terminal overvoltage on longer cable runs (up to about 100m, depending on cable capacitance). Power loss splits into 387W in the coil (copper losses) and 214W in the iron core (hysteresis and eddy-current losses), totaling roughly 600W at full load. That heat must be vented — in a sealed IP54 cabinet, factor this into the thermal budget or add forced air. The thermal class H insulation (180°C hot-spot) gives headroom for overloads, but the 40°C ambient limit is the design point; derate current above that. Termination is via flat-type connectors (busbar-style), not ring lugs or screw clamps. The panel builder needs to plan for bolted flat connections on the main circuit — not a terminal block. Dimensions are 0.35m wide, 0.32m high, and 0.22m deep, so it occupies a significant footprint on the backplate; check clearances for the flat connectors and bending radius of incoming cables.","metaTitle":"SIDAC 4EU3652-0AK00-1BA0 Output Reactor, 94A 3-Phase AC Chok","metaDescription":"SIDAC 4EU3652-0AK00-1BA0 output reactor, 3-phase AC, 94A max, 0.15mH, 8kHz switching frequency, IP00, flat terminals. Mature lifecycle, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.22m","Width":"0.35m","Height":"0.32m","Maximum":"94A","Minimum":"1 000Hz","Rated Value":"8 000Hz","Phase number":"3","Type of voltage":"AC","lifecycle_stage":"mature","Product brand name":"SIDAC","Product designation":"output reactor","Protection class IP":"IP00","Inductivity rated value":"0.00015H","Power loss [W] of the coil":"387W","Ambient temperature rated value":"40°C","Power loss [W] of the iron core":"214W","Thermal class acc. to IEC 60085":"H","Type of electrical connection for main current circuit":"flat connector"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=37816&mlfb=4EU3652-0AK00-1BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU3652-0AK00-1BA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 4EU3652-0AK00-1BA0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ. Submit a request for quote (RFQ) through the storefront; availability and current pricing are confirmed at quote time. No stock figures or price lists are published here."},{"question":"What is the 4EU3652-0AK00-1BA0's depth and width for panel layout?","answer":"The depth is 0.22m and the width is 0.35m, with a height of 0.32m. This is a substantial open-frame reactor — plan for bolted flat-type connections and adequate ventilation clearance around the unit."},{"question":"What compliance documentation does this brand provide?","answer":"The product carries the SIDAC brand and is designed to EN 61558-2-20 for chokes. For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration at quote time — these are typically available per lot."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU3652-0AK00-1BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU3652-0AK00-1BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}