{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU3652-0AP00-4BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU3652-0AP00-4BA0","canonicalUrl":"https://aoctrl.com/siemens/4EU3652-0AP00-4BA0","factsUrl":"https://aoctrl.com/api/mcp/products/4EU3652-0AP00-4BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIDAC output reactor, 3-phase, 400V, 117A max, 8kHz switching frequency, 0.1mH, IP00, flat-type terminals.","salesMarkdown":"The Siemens SIDAC 4EU3652-0AP00-4BA0 is a 3-phase output reactor rated for 117 A maximum continuous current and an 8 kHz switching frequency. It carries 0.1 mH inductance per phase and is built to thermal Class H (180 °C) per IEC 60085, with a combined copper and iron-core power loss of 400 W at rated load. Rated for 400 V AC line-to-line, this reactor sits between the drive output and the motor leads. Its job is to limit the rate of voltage rise (dV/dt) from the PWM waveform and reduce capacitive coupling currents in long motor cables. The 8 kHz switching frequency matches the typical IGBT carrier frequency of modern variable-frequency drives — if your drive runs a higher carrier (12–16 kHz), the core losses will increase and you may need to derate the current. For a motor drive application, the motor full-load current should stay at or below this figure. The 0.1 mH inductance is relatively low — typical for reactors sized to handle high currents without excessive voltage drop. At 8 kHz, the impedance per phase is about 5 Ω, which provides moderate dV/dt suppression for cable runs up to roughly 100 m. For longer cable runs or higher carrier frequencies, a higher inductance value would be needed. The IP00 protection class means the reactor has no enclosure — the windings and core are exposed. The flat-type terminals accept busbar or large cable lugs; plan for adequate clearance around the terminals per IEC 61439. The SIDAC series covers a range of output reactors, and this 117 A, 0.1 mH variant occupies a specific slot in that lineup — sized for mid-power drives (roughly 55–75 kW depending on motor current). If your BOM calls for this exact order code, the ratings confirm fit: 3-phase, 400 V, 8 kHz switching frequency, flat terminals. No substitution guesswork needed.","metaTitle":"Siemens SIDAC 4EU3652-0AP00-4BA0 Output Reactor, 117A, 8kHz","metaDescription":"Siemens SIDAC 4EU3652-0AP00-4BA0 output reactor. 3-phase, 117A max, 8kHz switching frequency, 0.1mH, IP00, Class H insulation. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.22m","Width":"0.35m","Height":"0.32m","Maximum":"117A","Rated Value":"8 000Hz","Phase number":"3","Type of voltage":"AC","lifecycle_stage":"mature","Product brand name":"SIDAC","Product designation":"output reactor","Protection class IP":"IP00","Inductivity rated value":"0.0001H","Power loss [W] of the coil":"223W","Ambient temperature rated value":"40°C","Power loss [W] of the iron core":"177W","Thermal class acc. to IEC 60085":"H","Type of electrical connection for main current circuit":"flat connector"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=460531&mlfb=4EU3652-0AP00-4BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU3652-0AP00-4BA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 4EU3652-0AP00-4BA0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What is the 4EU3652-0AP00-4BA0 used for?","answer":"It is a 3-phase output reactor (also called a motor choke) installed between a variable-frequency drive and the motor. It limits dV/dt stress on motor insulation and reduces bearing currents caused by high-frequency PWM switching."},{"question":"What compliance documentation is available for 4EU3652-0AP00-4BA0?","answer":"The reactor is designed to EN 61558-2-20 and UL 506 standards. For specific RoHS, REACH, or CE declarations, request the manufacturer's compliance documentation with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU3652-0AP00-4BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU3652-0AP00-4BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}