{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU3652-0AP02-4BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU3652-0AP02-4BA0","canonicalUrl":"https://aoctrl.com/siemens/4EU3652-0AP02-4BA0","factsUrl":"https://aoctrl.com/api/mcp/products/4EU3652-0AP02-4BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIDAC output reactor, 3-phase, 117A max, 8000Hz rated frequency, IP00, flat connector terminals.","salesMarkdown":"## What this output reactor does in the drive line The Siemens SIDAC 4EU3652-0AP02-4BA0 is a 3-phase output reactor rated for 117 A maximum continuous current at 400 V AC, with a rated switching frequency of 8000 Hz. It sits between the VFD output and the motor cable to limit the rate of voltage rise (dV/dt) and reduce reflected-wave peaks on long cable runs — a common cause of motor winding insulation stress in PWM drives. The 0.1 mH inductance (0.0001 H) and 38.4 % impedance (UK) are sized to match the drive's carrier frequency and cable length, not the motor full-load amps alone. Total power loss at rated load splits between the coil (223 W) and the iron core (177 W), giving 400 W of heat to vent from the enclosure. Thermal class H (180 °C winding rise per IEC 60085) means the reactor can run hot without degrading the magnet wire insulation — important when the panel ambient hits 40 °C and the reactor is mounted near other heat sources. The flat-type main-circuit terminals accept busbar or cable lugs; plan for a 0.35 m width and 0.32 m height footprint on the backplate, with 0.22 m depth clearance for the winding overhang. Mount the reactor on the backplate inside a ventilated cabinet — IP00 means no touch protection, so the live flat terminals must be shielded by the panel door or a separate guard. The 0.35 m width and 0.32 m height fit a standard 600 mm wide enclosure with room for cable entry below. Flat-type terminals suit busbar connection from the drive output; torque values follow the lug manufacturer's spec for the cable cross-section used. The 8000 Hz rated frequency matches most IGBT-based VFDs running a standard 4 kHz to 8 kHz carrier. If the drive is set to a higher carrier (12 kHz or 16 kHz), derate the reactor's current or verify with the drive manufacturer — the core losses scale with frequency.","metaTitle":"Siemens SIDAC 4EU3652-0AP02-4BA0 Output Reactor, 117A, 3-Pha","metaDescription":"Siemens SIDAC 4EU3652-0AP02-4BA0 output reactor. 3-phase, 117A max, 8000Hz rated frequency, IP00. Mature lifecycle; sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.22m","Width":"0.35m","Height":"0.32m","Maximum":"117A","Rated Value":"8 000Hz","Phase number":"3","Type of voltage":"AC","lifecycle_stage":"mature","Product brand name":"SIDAC","Product designation":"output reactor","Protection class IP":"IP00","Inductivity rated value":"0.0001H","Power loss [W] of the coil":"223W","Ambient temperature rated value":"40°C","Power loss [W] of the iron core":"177W","Thermal class acc. to IEC 60085":"H","Type of electrical connection for main current circuit":"flat connector"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=26183&mlfb=4EU3652-0AP02-4BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU3652-0AP02-4BA0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this output reactor?","answer":"3-phase, 117 A maximum current at 400 V AC, 8000 Hz rated switching frequency, 0.1 mH inductance, 38.4 % impedance, thermal class H, IP00 protection."},{"question":"Where can I buy 4EU3652-0AP02-4BA0 and how is it quoted?","answer":"This part is sourced through independent distribution channels. Submit an RFQ for current availability and pricing — confirmed at quote time, no stock figures on this page."},{"question":"What physical space does this reactor need in the panel?","answer":"Footprint is 0.35 m wide by 0.32 m tall, with 0.22 m depth clearance for the winding. IP00 means it must be inside a sealed cabinet."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU3652-0AP02-4BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU3652-0AP02-4BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}