{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU3652-0AS00-4BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU3652-0AS00-4BA0","canonicalUrl":"https://aoctrl.com/siemens/4EU3652-0AS00-4BA0","factsUrl":"https://aoctrl.com/api/mcp/products/4EU3652-0AS00-4BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIDAC output reactor, 4EU3652-0AS00-4BA0, 3-phase AC, 80A max, 8kHz rated switching frequency, 0.3mH, IP00, class H insulation.","salesMarkdown":"## What this output reactor does on your drive line The Siemens SIDAC 4EU3652-0AS00-4BA0 is a 3-phase output reactor rated for 80 A maximum continuous current and a switching frequency of 8 kHz, with an inductance of 0.3 mH. It sits between the VFD output and the motor leads to limit the rate of voltage rise (dV/dt) and reduce reflected-wave stress on motor insulation — a common fix on long cable runs or when feeding a motor that wasn't designed for IGBT switching edges. The 0.3 mH inductance is sized for the 8 kHz carrier, so it knocks down the high-frequency content without dropping too much voltage at line frequency. Rated ambient is 40 °C, and the thermal class H winding (180 °C hot-spot) gives it headroom in a crowded cabinet. The IP00 enclosure means it's open-frame — plan for panel clearance and keep conductive debris off the windings. Terminals are flat-type connectors, so you'll need ring or fork lugs, not spring-cage. The 80 A maximum is the thermal current rating (Ith) at 40 °C ambient. For a drive feeding a motor, you'd typically size this so the motor FLA stays under 80 A — it's not a short-time overload rating. The 8 kHz switching frequency matches the carrier of most modern IGBT drives; if your drive runs a different carrier (say 4 kHz or 12 kHz), the reactor still works but the effective inductance at that frequency shifts slightly. The 0.3 mH value is a common sweet spot for cable runs up to about 100 m on 400 V class drives. Physical footprint: 0.35 m wide, 0.32 m tall, 0.22 m deep. That's a substantial block — roughly 14 by 13 by 9 inches. Make sure the panel backplate or mounting rail has the clear space before you cut the gland plate. The flat-type terminals need access for a wrench; don't bury it against a sidewall. ## Where it goes — deployment context This output reactor is a panel-mount component — no DIN rail clip, no chassis tabs. It's designed to be bolted to a backplate or mounted on its own bracket inside the enclosure. Typical install: between the drive output terminals and the motor cable gland plate, as close to the drive as cable bending radius allows.","metaTitle":"Siemens SIDAC 4EU3652-0AS00-4BA0 Output Reactor, 80A, 8kHz","metaDescription":"Siemens SIDAC 4EU3652-0AS00-4BA0 output reactor, 3-phase AC, 80A max, 8kHz rated switching frequency, 0.3mH, IP00, class H. Mature lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.22m","Width":"0.35m","Height":"0.32m","Maximum":"80A","Minimum":"1 200Hz","Rated Value":"8 000Hz","Phase number":"3","Type of voltage":"AC","lifecycle_stage":"mature","Product brand name":"SIDAC","Product designation":"output reactor","Protection class IP":"IP00","Inductivity rated value":"0.0003H","Ambient temperature rated value":"40°C","Thermal class acc. to IEC 60085":"H","Type of electrical connection for main current circuit":"flat connector"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=3493&mlfb=4EU3652-0AS00-4BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU3652-0AS00-4BA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 4EU3652-0AS00-4BA0?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels — no blanket stock count is published for this mature-line item."},{"question":"What are the key specifications of 4EU3652-0AS00-4BA0?","answer":"It is a 3-phase AC output reactor rated 80 A maximum, 8 kHz switching frequency, 0.3 mH inductance, IP00 enclosure, class H insulation, with flat-type terminals. Dimensions are 0.35 m wide by 0.32 m tall by 0.22 m deep."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU3652-0AS00-4BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU3652-0AS00-4BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}