{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU3652-0AV00-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU3652-0AV00-0AA0","canonicalUrl":"https://aoctrl.com/siemens/4EU3652-0AV00-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/4EU3652-0AV00-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens reactor, 3-phase, 400 V AC, 324 A rated, 0.16 mH, IP00, thermal class H, flat-type terminals.","salesMarkdown":"The Siemens 4EU3652-0AV00-0AA0 is a 3-phase line reactor (choke) rated for 324 A continuous at 400 V AC, with an inductance of 0.16 mH. It's designed to sit between a drive and the supply line, smoothing current and limiting harmonics or fault current rise rates. The 360 A maximum rating gives headroom for short-duration overloads without saturating the core. The 324 A rated current (I LN) is the continuous thermal rating at 40 °C ambient — this is the number to match against your drive's input current, not the motor FLA. The 360 A maximum (I thmax) is the thermal limit for short-term overloads, typically 1.5× for one minute per IEC. The 0.16 mH inductance is fixed; no taps. That value determines the voltage drop at rated current (about 3–4% at 50 Hz) and the harmonic attenuation — lower inductance means less filtering, so verify it matches your drive manufacturer's minimum impedance requirement. IP00 — no enclosure, no drip shield. This reactor mounts inside a cabinet, not on the wall or in a wet area. The flat-type terminals accept busbar or large cable lugs, not spring-cage or screw-clamp connectors. Plan for 0.35 m width, 0.321 m height, and 0.227 m depth on the mounting plate. At 2,927 W total power loss (2,830 W in the coil, 97 W in the iron core), it dumps significant heat into the enclosure — forced ventilation or a derated cabinet is non-negotiable at full load.","metaTitle":"Siemens 4EU3652-0AV00-0AA0 Reactor, 324 A, 0.16 mH, 400 V AC","metaDescription":"Siemens 4EU3652-0AV00-0AA0 3-phase line reactor. Rated 324 A, 0.16 mH, 400 V AC, IP00, thermal class H. Mature lifecycle; sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.227m","Width":"0.35m","Height":"0.321m","Maximum":"360A","Minimum":"1 200Hz","Rated Value":"324A","Phase number":"3","Power loss [W]":"2 927W","Type of voltage":"AC","lifecycle_stage":"mature","Product designation":"reactor","Protection class IP":"IP00","Inductivity rated value":"0.00016H","Power loss [W] of the coil":"2 830W","Ambient temperature rated value":"40°C","Power loss [W] of the iron core":"97W","Thermal class acc. to IEC 60085":"H","Type of electrical connection for main current circuit":"flat connector"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=74209&mlfb=4EU3652-0AV00-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU3652-0AV00-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What are the key specifications of the 4EU3652-0AV00-0AA0?","answer":"It is a 3-phase line reactor rated 324 A continuous at 400 V AC, with 0.16 mH inductance, 360 A maximum current, IP00 protection, thermal class H insulation, and flat-type terminals. Dimensions are 0.35 m wide, 0.321 m tall, and 0.227 m deep."},{"question":"Where can I buy the 4EU3652-0AV00-0AA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."},{"question":"What is the power loss of this reactor?","answer":"Total power loss is 2,927 W at rated load, with 2,830 W in the coil and 97 W in the iron core. This heat must be managed in the enclosure design."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU3652-0AV00-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU3652-0AV00-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}