{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU3652-6UC00-1BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU3652-6UC00-1BA0","canonicalUrl":"https://aoctrl.com/siemens/4EU3652-6UC00-1BA0","factsUrl":"https://aoctrl.com/api/mcp/products/4EU3652-6UC00-1BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 4EU3652-6UC00-1BA0 mains choke (line reactor) for variable-frequency drives, 3-phase, 630 A max / 567 A rated, 480 V AC, 0.044 mH, IP00, flat-type terminals.","salesMarkdown":"## What this reactor does and how it fits It limits harmonic distortion and reduces peak currents. The 630 A maximum rating and 567 A nominal current size it for large drives on 400/480 V AC three-phase systems. The 630 A maximum likely represents a short-time or overload ceiling; do not plan continuous duty above the 567 A figure. Total power loss is 564 W (394 W coil + 170 W iron core), all dissipated as heat inside the enclosure. That is substantial — forced ventilation or a derated panel fill factor is non-negotiable. The 4% voltage drop at rated current means the drive sees about 461 V on a 480 V line; factor that into your motor terminal voltage calculation. IP00 protection means no enclosure — the reactor is an open-frame component. The flat-type connectors are heavy-duty bus-bar lugs, not screw terminals; plan your cable terminations accordingly. Dimensions are 0.35 m wide × 0.321 m tall × 0.237 m deep — about the size of a small suitcase. Verify your gland plate and bus-bar routing before committing the panel layout.","metaTitle":"Siemens 4EU3652-6UC00-1BA0 Mains Choke, 630A, 480V AC, 3-Pha","metaDescription":"Siemens 4EU3652-6UC00-1BA0 mains choke (line reactor) for variable frequency drives. Rated 630A max, 567A nominal, 480V AC, 3-phase, 0.044 mH. IP00, flat connectors. UL/CSA recogni","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.237m","Width":"0.35m","Height":"0.321m","Maximum":"630A","Rated Value":"567A","Phase number":"3","Type of voltage":"AC","lifecycle_stage":"mature","Product designation":"Netzdrossel f. FU","Protection class IP":"IP00","Inductivity rated value":"0.000044H","Power loss [W] of the coil":"394W","Operating voltage rated value":"400, 480V","Ambient temperature rated value":"40°C","Operating frequency rated value":"50 ... 60Hz","Power loss [W] of the iron core":"170W","Thermal class acc. to IEC 60085":"H","Type of electrical connection for main current circuit":"flat connector","Relative inductive drop in voltage on the measurement level current, voltage and frequency":"4%"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=286001&mlfb=4EU3652-6UC00-1BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU3652-6UC00-1BA0/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does Siemens provide for the 4EU3652-6UC00-1BA0?","answer":"The part is UL/CSA recognized and designed to EN 61558-2-20. Standard Siemens documentation includes the declaration of conformity and manufacturer's declaration for RoHS/REACH compliance."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU3652-6UC00-1BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU3652-6UC00-1BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}