{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU3951-5UB00-0A","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU3951-5UB00-0A","canonicalUrl":"https://aoctrl.com/siemens/4EU3951-5UB00-0A","factsUrl":"https://aoctrl.com/api/mcp/products/4EU3951-5UB00-0A","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 4EU3951-5UB00-0A mains choke for frequency converters, 3-phase, 500V AC, 1120A max current, 1008A rated, 50Hz, 2% voltage drop, IP00, UL/CSA recognized.","salesMarkdown":"It sits between the supply and the drive, smoothing current harmonics and limiting inrush — a standard fit for any VFD cabinet that needs to meet IEEE 519 or just keep the drive from nuisance-tripping upstream breakers. IP00 means it's an open-frame component — no enclosure, no finger-safe cover. It mounts inside a cabinet, not on the wall. The flat-type terminals are heavy-duty bus-bar style, sized for the 1120 A path; you'll bolt copper bars or cable lugs directly, not land wire in a spring cage. Dimensions are 0.41 m wide by 0.385 m tall by 0.229 m deep — that's a substantial block, roughly 16 by 15 by 9 inches. Plan for adequate clearance around it: the iron core and coil together dissipate 545 W at full load (385 W coil loss plus 160 W iron loss), so forced ventilation or a derated ambient is expected. The 40 °C ambient rating is the reference; push above that and the current must be derated per the thermal class H insulation curve.","metaTitle":"Siemens 4EU3951-5UB00-0A Mains Choke, 1120A, 500V, 3-Phase","metaDescription":"Siemens 4EU3951-5UB00-0A mains choke for drives, 3-phase, 500V AC, 1120A max, 1008A rated, 50Hz, IP00, UL/CSA recognized. Mature lifecycle, sourced to order. Request RFQ for curren","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"0.229 m","Width":"0.41 m","Height":"0.385 m","IP Rating":"IP00","Product Status":"Mature"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=454900&mlfb=4EU3951-5UB00-0A","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU3951-5UB00-0A/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU3951-5UB00-0A","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU3951-5UB00-0A when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}