{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EU3951-6UA00-0A","brand":"Siemens","brandSlug":"siemens","productSlug":"4EU3951-6UA00-0A","canonicalUrl":"https://aoctrl.com/siemens/4EU3951-6UA00-0A","factsUrl":"https://aoctrl.com/api/mcp/products/4EU3951-6UA00-0A","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 4EU3951-6UA00-0A mains choke for frequency converters, 3-phase, AC, 710 A max, 400/480 V, 39 µH, 4% voltage drop, IP00, flat-type terminals.","salesMarkdown":"## Line reactor for drive input harmonics The Siemens 4EU3951-6UA00-0A is a three-phase mains choke (line reactor) rated for 710 A AC maximum current at 400/480 V AC, 50/60 Hz. It sits between the supply and a frequency converter to limit harmonic distortion, reduce voltage notching, and protect the drive DC bus from line transients. Total power loss runs 730 W (540 W coil + 190 W iron core) at 40 °C ambient, thermal class H insulation per IEC 60085. That means the winding can sustain 180 °C hot-spot temperature — adequate for continuous duty inside a ventilated cabinet. The IP00 open-frame construction requires the panel builder to provide finger-safe clearance or a separate enclosure; this is not a stand-alone device. Main circuit connection uses flat-type terminals. The 0.229 m depth, 0.41 m width, and 0.385 m height require a dedicated mounting plate. The 639 A operational current (I LN) is the rated continuous current at the nominal 4% voltage drop; if your drive draws 639 A or less, the reactor stays within its design impedance. Above that, the voltage drop climbs and the core may saturate earlier. The 4% relative inductive voltage drop (Uk) at rated current is a standard value for drive input reactors. It provides enough impedance to attenuate the 5th and 7th harmonics that dominate a 6-pulse rectifier input, without dropping so much voltage that the DC bus undervolts during heavy load. If your application requires tighter harmonic control (IEEE 519 compliance), you may need a higher-impedance reactor or a multi-pulse drive — but for most industrial VFD installations, 4% is the sweet spot.","metaTitle":"Siemens 4EU3951-6UA00-0A Mains Choke, 710 A, 400/480 V AC","metaDescription":"Siemens 4EU3951-6UA00-0A mains choke for frequency converters. 3-phase, 710 A AC max, 400/480 V AC, 39 µH, 4% voltage drop, IP00. Mature lifecycle, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"0.229 m","Width":"0.41 m","Height":"0.385 m","IP Rating":"IP00","Product Status":"Mature"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=24196&mlfb=4EU3951-6UA00-0A","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EU3951-6UA00-0A/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EU3951-6UA00-0A","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EU3951-6UA00-0A when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}