{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SJ4113-8HG40","brand":"Siemens","brandSlug":"siemens","productSlug":"5SJ4113-8HG40","canonicalUrl":"https://aoctrl.com/siemens/5SJ4113-8HG40","factsUrl":"https://aoctrl.com/api/mcp/products/5SJ4113-8HG40","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SJ4 series, miniature circuit breaker, 1-pole, 13 A, D characteristic, 10 kA breaking capacity per EN 60898, 15 kA per IEC 60947-2, 400 V AC, 18 mm wide.","salesMarkdown":"That D curve means it's built for loads with high inrush: motor starters, small transformers, discharge lighting. The magnetic trip holds through the startup surge and clears on a hard fault. Snaps onto standard DIN rail — 18 mm width, one width unit. Mounting position any, so vertical or horizontal busbars work. Depth is 70 mm, same as installation depth; the combined tunnel terminals top and bottom take Cu conductors up to the rated torque of 3.5 Nm. The D characteristic (10–20× In magnetic trip) is the key selection parameter: if your load is a resistive heater or a general-purpose outlet, you want B or C curve — D is for inductive kicks. For DC circuits, the maximum rated voltage is 60 V — relevant if this lands in a control panel with a 48 VDC bus.","metaTitle":"Siemens 5SJ4113-8HG40 SENTRON MCB, 1P 13A D-curve, 10kA","metaDescription":"Siemens 5SJ4113-8HG40 SENTRON miniature circuit breaker, 1-pole 13 A, D tripping characteristic, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC. Current production. Sourced to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"70 mm","Poles":"1","Width":"18 mm","Height":"90 mm","Mounting":"on standard mounting rail","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"-25 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$77.65","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c2743d89fe2103ad56acb11b8802dc4f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=376285&mlfb=5SJ4113-8HG40","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SJ4113-8HG40/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SJ4113-8HG40","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SJ4113-8HG40 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}