{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SJ4230-8HG41","brand":"Siemens","brandSlug":"siemens","productSlug":"5SJ4230-8HG41","canonicalUrl":"https://aoctrl.com/siemens/5SJ4230-8HG41","factsUrl":"https://aoctrl.com/api/mcp/products/5SJ4230-8HG41","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SJ4 miniature circuit breaker, 2-pole, D-tripping characteristic, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC / 60 V DC, 2 MW, DIN rail mount.","salesMarkdown":"Rated 10 kA breaking capacity per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC, it handles fault currents up to those levels without upstream coordination issues. The 2-pole form switches both phase conductors; no neutral pole is built in. The D-curve is the headline selection parameter here. Unlike a B-curve (for resistive/lighting loads) or C-curve (general-purpose), the D-curve's magnetic trip threshold of 10–20× In is sized for motor feeders and transformer primaries where the inrush can hit 12× full-load current for a few cycles. If your BOM calls for a D-curve MCB, this is the correct family — swapping to a C-curve risks nuisance tripping on start-up. The 10 kA (EN 60898) and 15 kA (IEC 60947-2) ratings cover the two common certification regimes; the higher IEC figure matters for industrial installations where the prospective short-circuit current exceeds 10 kA. Rated operational voltage is 400 V AC and 60 V DC. The DC rating is limited to 60 V — not a 125 V DC rail breaker. For DC circuits at higher voltages, a different 5SJ4 variant with a higher DC rating is needed. Mounting position is unrestricted — vertical, horizontal, or upside-down; the mechanism works the same. Depth is 70 mm, which matches the standard 70 mm installation depth for most 5SJ4 enclosures. IP20 at the terminals (finger-safe with connected conductors) and IP40 in the handle area — fine for enclosed panels; not rated for washdown.","metaTitle":"Siemens 5SJ4230-8HG41 SENTRON MCB, 2-Pole, D-Curve, 10 kA","metaDescription":"Siemens 5SJ4230-8HG41 SENTRON miniature circuit breaker, 2-pole, D-curve, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC, 60 V DC. IP20/IP40, DIN rail. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"70 mm","Poles":"2","Width":"36 mm","Height":"110 mm","Mounting":"on standard mounting rail","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$104.14","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/20381090046dc20ef17ec28f0fd2611d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=94155&mlfb=5SJ4230-8HG41","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SJ4230-8HG41/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SJ4230-8HG41","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SJ4230-8HG41 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}