{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SJ4360-8HG41","brand":"Siemens","brandSlug":"siemens","productSlug":"5SJ4360-8HG41","canonicalUrl":"https://aoctrl.com/siemens/5SJ4360-8HG41","factsUrl":"https://aoctrl.com/api/mcp/products/5SJ4360-8HG41","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SJ4 series, 3-pole miniature circuit breaker, 60 A, D characteristic, 10 kA breaking capacity per EN 60898, 15 kA per IEC 60947-2, 3-module width.","salesMarkdown":"## D-curve trip for motor and transformer starts That D-curve means it tolerates the inrush of motor and transformer loads — typically 10 to 14 times rated current for a short duration — without nuisance tripping on startup. Rated 400 V AC and 60 V DC, it covers standard 3-phase panel feeds and some DC branch circuits. ## Breaking capacity: EN 60898 vs IEC 60947-2 For DC branch protection, the rated voltage is 60 V — confirm the system voltage stays within that limit. ## Active production, sourced per RFQ If you are replacing an existing breaker in a panel, verify the 54 mm width (3-module) fits the existing DIN-rail space and that the D-curve matches the load type. IP20 with connected conductors, IP40 in the handle area — suitable for enclosed industrial panels where the breaker is not exposed to washdown. Vibration resistance is 50 m/s² at 25 to 150 Hz, and 60 m/s² at 35 Hz for 4 seconds — adequate for machine-mounted panels on pumps or conveyors. Sealable for lockout/tagout compliance.","metaTitle":"Siemens 5SJ4360-8HG41 60A 3-Pole MCB, D Curve, 10kA EN","metaDescription":"Siemens SENTRON 5SJ4360-8HG41 60A 3-pole MCB with D tripping characteristic. 10 kA per EN 60898, 15 kA per IEC 60947-2. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"70 mm","Width":"54 mm","Height":"110 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"3P","Number Of Poles":"3","lifecycle_stage":"current","Fastening Method":"on standard mounting rail","Mounting Position":"any","at AC rated value":"400 V","at DC rated value":"60 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breakers","protection class IP":"IP20, with connected conductors, IP 40 in the handle range","Overvoltage Category":"3","Tunnel Terminals Top":"No","Vibration Resistance":"50 m/s² at 25 to 150Hz and 60m/s² at 35Hz (4sec)","Combined Terminal Top":"Yes","Design Of The Product":"Miniature circuit-breaker 5SJ4","Product Function Note":"Terminal tightening torque for Cu, 60/75°C; 3.5Nm/31lb.in","Tunnel Terminals Bottom":"No","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","at DC rated value maximum":"60 V","Neutral Conductor Switching":"No","Number Of Modular Width Units":"3","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"D","according to EN 60898 rated value":"10 kA","Ambient Temperature During Operation":"max. 95% humidity","Supply Voltage Frequency Rated Value":"50 Hz","according to IEC 60947-2 rated value":"15 kA","installation environment regarding EMC":"Suitable for environment B (immunity to interference not applicable)","insulation voltage (Ui) at AC rated value":"440 V","Value Range Of The Supply Voltage Frequency":"50/60 Hz","vibration resistance according to IEC 60068-2-6":"±1 mm at 5 to 25 Hz; 50 m/s² at 25 to 150 Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Tightening Torque With Screw-Type Terminals Maximum":"3.5 N·m","power loss [W] for rated value of the current at AC in hot operating state per pole":"6.5 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$700.86","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7bf1ca056547efeda25405df2b04aba7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=258994&mlfb=5SJ4360-8HG41","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SJ4360-8HG41/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SJ4360-8HG41 and get a price?","answer":"The 5SJ4360-8HG41 is sourced to order against an RFQ through independent distribution. Submit your BOM quantity for a current price and lead-time confirmation — no stock-holding claim is made here."},{"question":"Is 5SJ4360-8HG41 suitable for DC applications?","answer":"Yes, it is rated for DC circuits up to 60 V. For DC branch protection, confirm the system voltage does not exceed 60 V and that the D-curve's magnetic trip threshold is appropriate for the DC load profile."},{"question":"What is the breaking capacity of 5SJ4360-8HG41?","answer":"10 kA per EN 60898 for standard commercial installations, and 15 kA per IEC 60947-2 for industrial panel applications. The higher 15 kA figure applies when the prospective fault current exceeds 10 kA."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SJ4360-8HG41","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SJ4360-8HG41 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}