{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL1116-6MB","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL1116-6MB","canonicalUrl":"https://aoctrl.com/siemens/5SL1116-6MB","factsUrl":"https://aoctrl.com/api/mcp/products/5SL1116-6MB","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL1116-6MB miniature circuit breaker, 1-pole, B-curve, 16 A, 3 kA interrupting capacity per IEC 60947-2, 230/400 V AC, 18 mm wide, IP20.","salesMarkdown":"## Siemens SENTRON 5SL1116-6MB — 1-pole B-curve MCB, 16 A, 3 kA The Siemens 5SL1116-6MB is a SENTRON miniature circuit breaker (MCB) with a single pole, B tripping characteristic, and a 16 A rated current. It interrupts faults up to 3 kA per IEC 60947-2 at 230/400 V AC, making it a standard overcurrent protector for residential and light commercial final circuits — lighting, socket outlets, and small appliance loads. The B-curve trips between 3 and 5 times rated current, so it clears inrush from resistive loads without nuisance tripping, but it is not intended for motor or transformer starting peaks (use C or D curve for those). Rated for 16 A at 30 °C ambient, the breaker occupies one modular width (18 mm) on a DIN rail, with an installation depth of 70 mm and overall depth of 76 mm. The IP20 enclosure (with connected conductors) is suitable for dry indoor panels; the sealable design allows the installer to lock the toggle position after commissioning, preventing unauthorised reset or isolation. ## Panel fit and ratings The breaker snaps onto a standard 35 mm DIN rail in any mounting position (horizontal, vertical, or flat). At 18 mm wide (1 MW), it fits a single-pole slot in a distribution board. The 70 mm installation depth leaves clearance behind the panel door for wiring and busbar connections. Pollution degree 2 and overvoltage category III cover fixed installations inside buildings — typical for a residential consumer unit or a small commercial sub-distribution board. Power dissipation is 1.9 W per pole at rated current in hot operating state, which matters for thermal derating when multiple breakers are ganged in a small enclosure. The mechanical service life is rated at 4 000 operating cycles — adequate for a protection device that operates infrequently, but not intended for frequent switching duty (use a contactor or switch-disconnector for that role).","metaTitle":"Siemens 5SL1116-6MB SENTRON MCB, 1P B 16A 3kA","metaDescription":"Siemens 5SL1116-6MB SENTRON miniature circuit breaker, 1-pole, B-curve, 16 A, 3 kA per IEC 60947-2, 230/400 V AC, 18 mm wide. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"1","Width":"18 mm","Height":"90 mm","IP Rating":"IP20","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/351ecb56ff08cf908ca9b086aeb8ca2f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1046701&mlfb=5SL1116-6MB","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL1116-6MB/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL1116-6MB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL1116-6MB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}