{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL3008-7KL","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL3008-7KL","canonicalUrl":"https://aoctrl.com/siemens/5SL3008-7KL","factsUrl":"https://aoctrl.com/api/mcp/products/5SL3008-7KL","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL3008-7KL, miniature circuit breaker compact, 1P+N, 8 A, C characteristic, 4.5 kA per EN 60898, 1 MW, IP20.","salesMarkdown":"The 8 A rating holds at 30 °C ambient; at 40 °C it derates to 7.52 A, and at 50 °C it drops to 7 A. The 1P+N configuration switches the phase and disconnects the neutral; the neutral pole is not overcurrent-protected, so this is for single-phase circuits where neutral switching is required for isolation. The installation depth behind the panel is 70 mm, so it fits most domestic enclosures without the cover fouling the busbar. Touch protection is built in — no exposed live metal when the toggle is in the off position. ## Where it goes and what it handles Siemens lists this for residential buildings and infrastructure — think final sub-circuits in apartment distribution boards, lighting and general-purpose socket outlets in commercial fit-outs, or small HVAC branch protection. The IP20 rating (with conductors connected) means it's for dry indoor enclosures only; no washdown or outdoor exposure without a secondary enclosure. It's sealable — a lead-seal wire can be passed through the toggle housing to lock the breaker in the off position for lockout/tagout.","metaTitle":"Siemens 5SL3008-7KL SENTRON MCB, 8A 1P+N C-Curve, 4.5kA","metaDescription":"Siemens 5SL3008-7KL SENTRON miniature circuit breaker, 8 A, 1P+N, C characteristic, 4.5 kA per EN 60898. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL3008-7KL","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"CIRCUIT BREAKER 230V 4.5KA, 1+N-POLE/1MW, N LEFT C8","Halogen-Free":"Yes","Silicon-Free":"Yes","Type Of Voltage":"AC","lifecycle_stage":"current","Fastening Method":"standard rail","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"8 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"No","Design Of The Product":"Miniature circuit breaker compact","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 30 °C / rated value":"8 A","at 40 °C / rated value":"7.52 A","at 45 °C / rated value":"7.26 A","at 50 °C / rated value":"7 A","at 55 °C / rated value":"6.73 A","at 60 °C / rated value":"6.45 A","Combined Terminal Bottom":"No","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"4.5 kA","Position / Of Power Supply Cord":"Any","Product Feature / Touch Protection":"Yes","Supply Voltage Frequency / Rated Value":"50/60 Hz","Influence Of The Surrounding Temperature":"45°C, max. 95% humidity","insulation voltage / at AC / rated value":"250 V","vibration resistance / acc. to IEC 60068-2-6":"Yes","with single-phase operation / at AC / maximum":"250 V","Product Function / Neutral Conductor Switching":"Yes","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8426e9aa8858e6c9744b8e9afe148b49.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1354185&mlfb=5SL3008-7KL"},"ai":{"faq":[{"question":"What is the depth of 5SL3008-7KL?","answer":"The depth is 76 mm overall. The installation depth behind the panel face is 70 mm, which is the dimension that matters for enclosure clearance."},{"question":"Will 5SL3008-7KL drop into a panel specified around 5SY6002-7KL without rewiring?","answer":"Both are 1-module-wide (18 mm) MCBs on standard DIN rail, so the mechanical fit is identical. The electrical substitution depends on the trip curve and ratings: the 5SL3008-7KL is an 8 A C-curve; verify that the original 5SY6002-7KL spec matches those parameters before swapping."},{"question":"Who supplies 5SL3008-7KL and how is it quoted for volume purchases?","answer":"We source this through independent distribution channels. Availability and current pricing are confirmed at quote time against an RFQ — submit a request for your target quantity and we'll return a firm price and lead time."},{"question":"What compliance documentation does Siemens provide for 5SL3008-7KL?","answer":"The breaker is designed to EN 60898 (the 4.5 kA rating is per that standard). It carries an IP20 protection class with conductors connected, and the materials are halogen-free and silicon-free. Specific RoHS/REACH declarations are typically available from Siemens on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL3008-7KL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL3008-7KL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}