{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL3113-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL3113-7","canonicalUrl":"https://aoctrl.com/siemens/5SL3113-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SL3113-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL3113-7, 1-pole miniature circuit breaker, 13 A rated, C tripping characteristic, 4.5 kA breaking capacity per EN 60898, 400 V AC.","salesMarkdown":"The Siemens SENTRON 5SL3113-7 is a 1-pole miniature circuit breaker (MCB) rated 13 A at 30 °C with a C tripping characteristic, meaning it trips at 5 to 10 times rated current — the standard choice for moderate inrush loads like small motors, lighting circuits, and general-purpose outlets in residential and light commercial panels. Rated current is 13 A at 30 °C ambient, but derates to 12.37 A at 40 °C and 11.36 A at 55 °C — a consideration when the breaker shares a crowded enclosure with other heat sources. Rated operational voltage is 400 V AC single-phase (250 V AC single-phase), with a maximum of 440 V AC for multi-phase operation. The DC rating is 72 V maximum — useful for control circuits but not for high-voltage DC bus protection. ## Physical fit and compliance Dimensions: 18 mm wide (1 modular unit), 90 mm high, 76 mm deep (installation depth 70 mm). Degree of pollution 2, overvoltage category III. Touch protection is built in. Halogen-free and silicon-free construction. Sealable (can be locked in the OFF position). Complies with IEC 81346-2 and DIN EN 61346-2 designation F.","metaTitle":"Siemens SENTRON 5SL3113-7 MCB, 1P, 13A, C-Curve, 4.5kA","metaDescription":"Siemens SENTRON 5SL3113-7 miniature circuit breaker, 1-pole, 13 A rated, C characteristic, 4.5 kA breaking capacity per EN 60898. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL3113-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 230/400 V 4.5 kA, 1-pole, C, 13A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"13 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 30 °C / rated value":"13 A","at 40 °C / rated value":"12.37 A","at 45 °C / rated value":"11.96 A","at 55 °C / rated value":"11.36 A","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"4.5 kA","acc. to IEC 60947-2 / rated value":"4.5 kA","Product Feature / Touch Protection":"Yes","supply voltage / at AC / rated value":"400 V","Type Of Voltage / Of The Operating Voltage":"AC","with multi-phase operation / at AC / maximum":"440 V","Product Component / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","with single-phase operation / at AC / rated value":"250 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7d9ebca4f405a59bd5cbb3ecb80ea7e8.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=101912&mlfb=5SL3113-7"},"ai":{"faq":[{"question":"Where can I buy 5SL3113-7 and how do I get a price?","answer":"The 5SL3113-7 is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"Will 5SL3113-7 drop into a panel that was specified around 5SL4120-7CC without rewiring?","answer":"Both are 1-pole SENTRON MCBs with the same 18 mm width and DIN-rail mounting, so the 5SL3113-7 will physically fit the same panel position. However, the 5SL4120-7CC is a 20 A B-curve device; the 5SL3113-7 is a 13 A C-curve — verify the load current and trip coordination before swapping."},{"question":"What is 5SL3113-7's listed depth (76 mm) on this component line?","answer":"The 5SL3113-7 has a depth of 76 mm (installation depth 70 mm)."},{"question":"What is 5SL3113-7's listed width (18 mm) on this component line?","answer":"The 5SL3113-7 has a width of 18 mm, occupying one modular unit on a DIN rail."},{"question":"What compliance documentation does this brand provide for 5SL3113-7 (RoHS, REACH, UL, IEC)?","answer":"The 5SL3113-7 is designed to EN 60898 and IEC 60947-2, with a 4.5 kA breaking capacity per both standards. It carries IP20 protection (with connected conductors), is halogen-free and silicon-free, and is rated for overvoltage category III, pollution degree 2. For specific RoHS/REACH/UL declarations, request the manufacturer's compliance documentation at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL3113-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL3113-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}