{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL3220-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL3220-7","canonicalUrl":"https://aoctrl.com/siemens/5SL3220-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SL3220-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL3220-7 miniature circuit breaker, 2-pole, C tripping characteristic, 20 A rated at 400 V AC, 4.5 kA breaking capacity per EN 60898.","salesMarkdown":"## What this MCB is and what it does The Siemens 5SL3220-7 is a 2-pole miniature circuit breaker from the SENTRON family, rated 20 A at 400 V AC with a C tripping characteristic. Per the datasheet, it breaks 4.5 kA under EN 60898 and 5 kA under IEC 60947-2 — the higher figure applies when the breaker is applied in an industrial distribution context where the standard allows it. The C-curve means it trips between 5 and 10 times rated current, so it handles moderate inrush from small motor or lighting loads without nuisance tripping, while still clearing a hard short within the rated interrupting capacity. ## Thermal derating and real-world current The 20 A rating holds at 30 °C ambient. At 40 °C the continuous current drops to 18.79 A; at 45 °C it's 18.6 A; at 55 °C it's 16.8 A. If the panel ambient runs above 30 °C — common in a crowded enclosure — the load current must be derated per these figures or the breaker will nuisance-trip on thermal overload. The mechanical service life is 10 000 switching cycles typical, which is adequate for a distribution board that sees infrequent manual operation. ## Mounting and integration The 5SL3220-7 occupies 2 modular width units (36 mm total) on a DIN rail. Installation depth is 70 mm; the overall depth including the front toggle is 76 mm. It mounts in any position and is rated IP20 with connected conductors — standard for a panelboard MCB, not for wet locations. Pollution degree 2 and overvoltage category III suit it for fixed-installation distribution boards in residential or light commercial infrastructure.","metaTitle":"Siemens 5SL3220-7 SENTRON MCB, 2-pole C 20 A, 400 V AC","metaDescription":"Siemens 5SL3220-7 SENTRON miniature circuit breaker, 2-pole, C-curve, 20 A rated at 400 V AC. Breaking capacity 4.5 kA per EN 60898. Current lifecycle stage. Available to order aga","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"2","Width":"36 mm","Height":"90 mm","IP Rating":"IP20","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/abe3bd82392c6e5e556af1de51bd959c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=70686&mlfb=5SL3220-7","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL3220-7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL3220-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL3220-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}