{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL3340-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL3340-6","canonicalUrl":"https://aoctrl.com/siemens/5SL3340-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SL3340-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL3340-6, miniature circuit breaker, 3-pole, B characteristic, 40 A rated current, 4.5 kA breaking capacity, 400 V AC.","salesMarkdown":"The Siemens 5SL3340-6 is a SENTRON miniature circuit breaker, 3-pole, B-curve, rated 40 A at 30 °C with a 4.5 kA breaking capacity per EN 60898 and IEC 60947-2. It's designed for 400 V AC three-phase circuits, with a maximum of 440 V AC in multi-phase operation. Rated 38.07 A at 40 °C and 34.97 A at 55 °C, so if your panel runs hot, you lose about 12% capacity at the upper end of the ambient range. ## Panel Fit & Installation Mounts on DIN rail in any position — 3 modular width units (54 mm wide), 76 mm deep, 90 mm tall, with an installation depth of 70 mm. IP20 with conductors connected, so it's for enclosed panels, not washdown areas. Touch protection is built in. Sealable, halogen-free, silicon-free — that's another SKU I don't need to worry about for sensitive environments like clean rooms or food processing lines. No neutral conductor switching on this 3-pole unit.","metaTitle":"Siemens 5SL3340-6 SENTRON MCB, 3P B 40A 4.5kA","metaDescription":"Siemens 5SL3340-6 SENTRON miniature circuit breaker, 3-pole, B-curve, 40 A rated, 4.5 kA breaking capacity per IEC/EN. Current lifecycle. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["3-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"54 mm","title":"5SL3340-6","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 4.5 kA, 3-pole, B, 40 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"3P","Number Of Poles":"3","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"40 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 30 °C / rated value":"40 A","at 40 °C / rated value":"38.07 A","at 45 °C / rated value":"36.8 A","at 55 °C / rated value":"34.97 A","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"3","Tripping Characteristic Class":"B","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"4.5 kA","acc. to IEC 60947-2 / rated value":"4.5 kA","Product Feature / Touch Protection":"Yes","supply voltage / at AC / rated value":"400 V","Type Of Voltage / Of The Operating Voltage":"AC","with multi-phase operation / at AC / maximum":"440 V","Product Component / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3b9df57720299236f2427975c518494f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=491239&mlfb=5SL3340-6"},"ai":{"faq":[{"question":"What is the breaking capacity of the 5SL3340-6?","answer":"The 5SL3340-6 has a 4.5 kA breaking capacity per both EN 60898 and IEC 60947-2. That means it can safely interrupt fault currents up to 4.5 kA at 400 V AC without welding contacts or cascading failure upstream."},{"question":"What does the B-curve characteristic mean for this breaker?","answer":"The B-curve trips at 3 to 5 times rated current (120 to 200 A for this 40 A unit). It's intended for resistive and light inductive loads like lighting circuits, socket outlets, and control transformers where inrush is low — not for motor starting or heavy transformer loads that would need a C or D curve."},{"question":"Will the 5SL3340-6 drop into a panel specified for 5SL4120-7CC?","answer":"Not without verifying the circuit requirements. The 5SL3340-6 is a 3-pole B-curve 40 A unit; the 5SL4120-7CC is a different variant. Check the pole count, curve, and current rating of your existing specification before substituting."},{"question":"What compliance documentation is available for the 5SL3340-6?","answer":"The 5SL3340-6 carries IEC 60947-2 and EN 60898 ratings, overvoltage category III, pollution degree 2, and is halogen-free and silicon-free. Standard SENTRON compliance documentation (CE, declaration of conformity) is available through the manufacturer's channels."},{"question":"Where can I buy the 5SL3340-6?","answer":"The 5SL3340-6 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL3340-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL3340-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}