{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL3506-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL3506-7","canonicalUrl":"https://aoctrl.com/siemens/5SL3506-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SL3506-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL3506-7 miniature circuit breaker, 1P+N, C-curve 6 A, 230 V AC, 4.5 kA breaking capacity, 2-module width.","salesMarkdown":"The Siemens SENTRON 5SL3506-7 is a miniature circuit breaker (MCB) in the 5SL series, rated 6 A at 230 V AC with a C tripping characteristic and a 1P+N pole configuration — meaning it switches both the line and neutral, with overcurrent protection only on the phase. ## Ratings that matter for the panel At 30 °C ambient the breaker carries a full 6 A; derate to 5.64 A at 40 °C, 5.4 A at 45 °C, and 5.04 A at 55 °C — a consideration if this lands in a crowded enclosure with other heat sources. The 1P+N design occupies 2 modular width units (36 mm wide, 76 mm deep, 70 mm installation depth), and the mounting position is unrestricted, so it fits any DIN-rail orientation. ## Construction and compliance details Sealable (tamper-evident provision), halogen-free and silicon-free construction, with touch protection on the terminals.","metaTitle":"Siemens SENTRON 5SL3506-7 MCB, C-Curve 6A 1P+N 230V 4.5kA","metaDescription":"Siemens SENTRON 5SL3506-7 miniature circuit breaker, 6A C-curve, 1P+N, 230V AC, 4.5kA breaking capacity. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SL3506-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 230 V 4.5 kA, 1+N-pole, C, 6A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"6 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 30 °C / rated value":"6 A","at 40 °C / rated value":"5.64 A","at 45 °C / rated value":"5.4 A","at 55 °C / rated value":"5.04 A","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"4.5 kA","acc. to IEC 60947-2 / rated value":"4.5 kA","Product Feature / Touch Protection":"Yes","supply voltage / at AC / rated value":"230 V","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","with single-phase operation / at AC / rated value":"250 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a6da88bfde3ef45218a663a46b07c453.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=321955&mlfb=5SL3506-7"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SL3506-7?","answer":"4.5 kA per both EN 60898 and IEC 60947-2, adequate for residential and light commercial service entrances."},{"question":"What is the temperature derating for this MCB?","answer":"Rated 6 A at 30 °C, derated to 5.64 A at 40 °C, 5.4 A at 45 °C, and 5.04 A at 55 °C."},{"question":"Where can I buy 5SL3506-7 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will 5SL3506-7 drop into a panel specified around 5SL6016-7KL?","answer":"Both are 2-module-width Siemens SENTRON MCBs with the same mounting footprint, so physical fit is the same. The difference is the electrical rating — confirm the load current and breaking capacity requirements match before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL3506-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL3506-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}