{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL3606-7MB","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL3606-7MB","canonicalUrl":"https://aoctrl.com/siemens/5SL3606-7MB","factsUrl":"https://aoctrl.com/api/mcp/products/5SL3606-7MB","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL3 miniature circuit breaker, 5SL3606-7MB, 4-pole (3P+N), C-curve, 6 A rated, 4.5 kA breaking capacity per EN 60898, 400 V AC.","salesMarkdown":"## Rated for the panel — 6 A C-curve, 4-pole, 4.5 kA That C-curve means it holds through mild inrush — motor starts, capacitor banks, transformer energization — and trips fast on a hard fault. The neutral pole switches (3P+N), so you get full isolation on all three phases plus the neutral — no shared busbar concerns on a TN or TT system. Ambient temperature range of -25 to +45 °C covers unconditioned enclosures and outdoor cabinets in moderate climates. IP20 with connected conductors — panel-internal duty only, not for wet locations without a separate enclosure. Snaps onto standard DIN rail. Width is 72 mm (4 width units). Sealable cover available for tamper-proofing in utility-metering or common-area distribution boards. Halogen-free and silicon-free construction for environments where outgassing matters (clean rooms, telecom shelters).","metaTitle":"Siemens 5SL3606-7MB SENTRON MCB, 4P C-6A, 4.5 kA","metaDescription":"Siemens SENTRON 5SL3606-7MB miniature circuit breaker, 4-pole C-curve 6 A, 4.5 kA breaking capacity per EN 60898. Active production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Solid":"0.75 ... 25 mm²","Width":"72 mm","title":"5SL3606-7MB","Height":"90 mm","Sealable":"Yes","Stranded":"0.75 ... 25 mm²","Rated Value":"50 Hz","description":"Miniature circuit breaker 400 V 4.5 kA, 3+N-pole, C, 6A","Halogen-Free":"Yes","Silicon-Free":"Yes","During Storage":"-40 ... +75 °C","Number of poles":"4","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Ambient temperature":"-25 ... +45 °C","Product designation":"Miniature circuit breaker","Protection class IP":"IP20, with connected conductors","Overvoltage category":"3","Design of the product":"5SL miniature circuit breakers","Energy limiting class":"3","Number of width units":"4","Number of poles / Note":"3P+N","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SL3","Suitability for operation":"Residential buildings/infrastructure","Current / at AC / rated value":"6 A","Tripping characteristic class":"C","at DC / rated value / maximum":"60 V","acc. to EN 60898 / rated value":"4.5 kA","acc. to IEC 60947-2 / rated value":"4.5 kA","Product feature / Touch protection":"Yes","Supply voltage / at AC / rated value":"400 V","with multi-phase operation / at AC / maximum":"440 V","Tightening torque / with screw-type terminals":"2.5 ... 3 N·m","Product function / neutral conductor switching":"Yes","with multi-phase operation / at AC / rated value":"440 V","Mechanical service life (switching cycles) / typical":"20 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9bc29662d04a65c14fa416333a7ce802.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=451780&mlfb=5SL3606-7MB"},"ai":{"faq":[{"question":"Where can I buy 5SL3606-7MB?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 5SL3606-7MB?","answer":"4.5 kA per EN 60898 and IEC 60947-2 at 400 V AC. That is the standard interrupting rating for this class of MCB."},{"question":"What wire sizes does 5SL3606-7MB accept?","answer":"Solid or stranded copper from 0.75 to 25 mm². Terminal torque spec is 2.5–3 N·m."},{"question":"Will 5SL3606-7MB fit in a panel designed for 5SL3640-7MB?","answer":"Both are 4-pole SENTRON MCBs in the same 5SL3 mechanical footprint — same width (72 mm), depth (76 mm), and DIN-rail mounting. The difference is the current rating: 6 A vs 40 A. If the panel busbar and load wiring are sized for 40 A, dropping in a 6 A breaker is fine; the reverse is not."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL3606-7MB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL3606-7MB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}