{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL3610-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL3610-7","canonicalUrl":"https://aoctrl.com/siemens/5SL3610-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SL3610-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL3610-7 miniature circuit breaker, 3P+N, C-curve, 10 A, 4.5 kA breaking capacity at 400 V AC, 4 MWU.","salesMarkdown":"## What it is and what it does The Siemens SENTRON 5SL3610-7 is a 3P+N miniature circuit breaker with C-curve trip characteristic, rated 10 A at 400 V AC and a breaking capacity of 4.5 kA per both EN 60898 and IEC 60947-2. It occupies 4 modular width units (72 mm) on the DIN rail and is designed for residential and infrastructure branch-circuit protection. The C-curve means it trips at 5 to 10 times rated current — typical for mixed resistive and moderate inductive loads like lighting, socket outlets, and small motor circuits where some inrush is expected. The 4.5 kA breaking capacity is the maximum fault current it can safely interrupt at 400 V AC; for installations with higher prospective fault current, a current-limiting upstream device is needed. ## Ratings and derating At 30 °C ambient the breaker carries its full 10 A rating. Above that, it derates: 9.52 A at 40 °C, 9 A at 45 °C, and 8.74 A at 55 °C. If the panel runs hot — say inside a sealed enclosure near other heat sources — use the 40 °C column for sizing. The operating temperature range is -40 to 75 °C, storage wider, but the derating curve is the one that governs continuous load. The breaker is rated for overvoltage category III and pollution degree 2, which covers fixed installations inside buildings where transient overvoltages are controlled by upstream SPDs. Touch protection is built in, and the housing is halogen-free and silicon-free — relevant for environments sensitive to outgassing, such as clean rooms or certain industrial zones. ## Mounting and integration Snaps onto standard 35 mm DIN rail. Depth is 76 mm, installation depth 70 mm — check the gland plate clearance if the panel has a shallow back. Mounting position is any, so vertical or horizontal orientation is fine. The neutral pole is switched (3P+N), meaning the N conductor is opened and closed with the phases, which is required in some regional wiring rules for TN-S or TT systems. Sealable — the toggle can be locked in the OFF position with a padlock or seal wire, useful for lockout/tagout during maintenance. IP20 with connected conductors means it's protected against finger contact but not against moisture; keep it inside a dry enclosure.","metaTitle":"Siemens 5SL3610-7 SENTRON MCB, 3P+N, C-Curve, 10 A, 4.5 kA","metaDescription":"Siemens 5SL3610-7 SENTRON miniature circuit breaker, 3P+N, 10 A, C-curve, 4.5 kA breaking capacity per EN 60898 & IEC 60947-2. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SL3610-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 4.5 kA, 3+N-pole, C, 10 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"3P+N","Number Of Poles":"4","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"10 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 30 °C / rated value":"10 A","at 40 °C / rated value":"9.52 A","at 45 °C / rated value":"9 A","at 55 °C / rated value":"8.74 A","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"4","Tripping Characteristic Class":"C","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"4.5 kA","acc. to IEC 60947-2 / rated value":"4.5 kA","Product Feature / Touch Protection":"Yes","supply voltage / at AC / rated value":"400 V","Type Of Voltage / Of The Operating Voltage":"AC","with multi-phase operation / at AC / maximum":"440 V","Product Component / Neutral Conductor Switching":"Yes","with multi-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4dcc175083a27b87fd05faca22837ee7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=88629&mlfb=5SL3610-7"},"ai":{"faq":[{"question":"Who supplies 5SL3610-7 and how is it quoted for volume purchases?","answer":"This part is sourced through independent distribution channels. Submit an RFQ for volume pricing and lead-time confirmation."},{"question":"What is 5SL3610-7's listed depth (76 mm) on this component line?","answer":"The depth is 76 mm, with an installation depth of 70 mm."},{"question":"What compliance documentation does this brand provide for 5SL3610-7 (RoHS, REACH, UL, IEC)?","answer":"The breaker is rated per EN 60898 and IEC 60947-2 for breaking capacity, and the housing is halogen-free and silicon-free. Specific RoHS/REACH declarations are available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL3610-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL3610-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}