{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL4101-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL4101-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SL4101-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL4101-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL4 series, miniature circuit breaker (MCB), 1-pole, 1 A rated, C-curve, 10 kA breaking capacity per EN 60898, 400 V AC, 1 MW wide, IP20, sealable.","salesMarkdown":"The Siemens 5SL4101-7CC is a SENTRON miniature circuit breaker (MCB) — one pole, rated 1 A at 400 V AC with a C-curve trip characteristic and 10 kA breaking capacity per EN 60898. It snaps onto DIN rail, occupies one modular width (18 mm), and is rated for residential buildings and infrastructure panels. The IP20 enclosure (with conductors connected) is standard for inside-the-panel mounting; no washdown rating here. At 1 A, that's 5 to 10 A magnetic trip; expect nuisance trips if you're feeding a pure resistive load with no startup surge. The 10 kA breaking capacity (per EN 60898) tells you it can safely interrupt a fault current up to 10,000 A at 400 V AC without welding contacts or cascading upstream — adequate for most residential and light commercial service entrances. Derating matters: at 30 °C ambient it carries the full 1 A; at 40 °C that drops to 0.95 A, at 45 °C to 0.92 A, at 50 °C to 0.89 A, and at 55 °C to 0.86 A. The thermal curve is the binding spec, not the 30 °C number. Single-phase operation is rated 250 V AC; multi-phase (two or three poles ganged) goes to 440 V AC. DC rating maxes at 72 V — fine for control circuits, not for a DC bus.","metaTitle":"Siemens 5SL4101-7CC SENTRON MCB, 1A C-Curve 10kA","metaDescription":"Siemens 5SL4101-7CC SENTRON miniature circuit breaker, 1-pole, 1 A, C-curve, 10 kA breaking capacity per EN 60898. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL4101-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 230/400 V 10kA, 1-pole, C, 1 A Circuit breaker 230/400 V 10kA, 1-pole, C, 1 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","at AC / rated value":"1 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","according to EN 61346-2":"F","at 30 °C / rated value":"1 A","at 40 °C / rated value":"0.95 A","at 45 °C / rated value":"0.92 A","at 50 °C / rated value":"0.89 A","at 55 °C / rated value":"0.86 A","according to IEC 81346-2":"F","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","at DC / rated value / maximum":"72 V","Product Feature / Touch Protection":"Yes","according to EN 60898 / rated value":"10 kA","supply voltage / at AC / rated value":"400 V","Type Of Voltage / Of The Operating Voltage":"AC","with multi-phase operation / at AC / maximum":"440 V","Product Component / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","vibration resistance / according to IEC 60068-2-6":"50 m/s² at 25 to 150 Hz","with single-phase operation / at AC / rated value":"250 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b740b0085421af97c0af69348f11467c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=264975&mlfb=5SL4101-7CC"},"ai":{"faq":[{"question":"Where can I buy 5SL4101-7CC and how do I get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"Will 5SL4101-7CC drop into a panel specified around 5SL3116-6MB without rewiring?","answer":"Both are 1-pole SENTRON MCBs on the same DIN-rail footprint (18 mm width per module), so mechanical fit is identical. The 5SL4101-7CC is a 1 A C-curve; verify the 5SL3116-6MB's rating and curve against your circuit's requirements before swapping — the physical swap is fine, but the protection parameters differ."},{"question":"What compliance documentation does this brand provide for 5SL4101-7CC?","answer":"The part carries EN 60898 certification for breaking capacity and is designed for residential/infrastructure use. It is halogen-free and silicon-free. Specific RoHS/REACH/UL declarations should be requested at quote time from the supplier."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL4101-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL4101-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}