{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL4106-7RC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL4106-7RC","canonicalUrl":"https://aoctrl.com/siemens/5SL4106-7RC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL4106-7RC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL4106-7RC, miniature circuit breaker, 1-pole, C characteristic, 6 A rated current, 10 kA breaking capacity at 240/415 V AC, 1 MW.","salesMarkdown":"The Siemens 5SL4106-7RC is a SENTRON miniature circuit breaker (MCB) — a single-pole, C-curve device rated 6 A with a 10 kA breaking capacity per EN 60898 at 240/415 V AC. This is the part you spec into a residential or light-commercial distribution board when you need a 1-module-width (18 mm) breaker that clears a 10 kA prospective fault current on a 240/415 V supply. The 10 kA breaking capacity at 240/415 V AC (per EN 60898) is the headline number: it tells you this MCB can safely interrupt a fault current up to 10,000 A without welding its contacts or failing catastrophically. That covers most residential and light-commercial service entrances in Europe and markets using the 240/415 V three-phase system. The 6 A rating on a C-curve means it will hold steady at 6 A continuous and trip on overloads above roughly 30 A (5× In) to 60 A (10× In) — a good fit for protecting a 1.5 mm² lighting circuit or a small pump motor. Rated insulation voltage is 440 V AC for multi-phase operation and 250 V AC for single-phase, so this breaker can be used on a 230/400 V three-phase system as a single-pole branch protector. The 50/60 Hz frequency range covers standard mains supplies globally. ## Physical integration and panel fit At 18 mm wide (1 modular unit), 90 mm tall, and 76 mm deep, the 5SL4106-7RC snaps onto a standard DIN rail (EN 60715) and occupies a single slot in a consumer unit or distribution board. Mounting position is unrestricted — horizontal, vertical, or flat — which simplifies panel layout. The 5SL4106-7RC carries an Active lifecycle status from Siemens. It is a current-production part in the SENTRON 5SL series, not subject to phase-out or last-time-buy. For a BOM that already qualifies this order code, there is no requalification trigger on the horizon.","metaTitle":"Siemens 5SL4106-7RC SENTRON MCB, 1P C 6A 10kA 240/415V","metaDescription":"Siemens 5SL4106-7RC SENTRON miniature circuit breaker, 1-pole, C-curve, 6A, 10kA breaking capacity per EN 60898 at 240/415V AC. Active production, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL4106-7RC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 240/415 V 10kA, 1-pole, C, 6A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","Suitability For Operation":"Residential buildings/infrastructure","at DC rated value maximum":"72 V","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","supply voltage at AC rated value":"415 V","according to EN 60898 rated value":"10 kA","Type Of Voltage Of The Operating Voltage":"AC","with multi-phase operation at AC maximum":"440 V","Value Range Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"250 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"0.86 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b740b0085421af97c0af69348f11467c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=327845&mlfb=5SL4106-7RC"},"ai":{"faq":[{"question":"Where can I buy 5SL4106-7RC and get a price?","answer":"The 5SL4106-7RC is sourced and quoted to order against an RFQ through independent distribution channels. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"Will 5SL4106-7RC drop into a panel specified around 5SL4363-7?","answer":"No — the 5SL4363-7 is a 3-pole breaker (54 mm wide, 3 modular units), while the 5SL4106-7RC is a single-pole unit (18 mm wide). The depth (76 mm) and height (90 mm) match, so the physical footprint on the DIN rail is the same, but the pole count and width are different. You cannot directly substitute one for the other without rewiring the circuit."},{"question":"What compliance documentation does Siemens provide for 5SL4106-7RC?","answer":"The 5SL4106-7RC is CE-marked for the European market and carries a 10 kA breaking capacity rating per EN 60898. The product is halogen-free and silicon-free. Specific RoHS, REACH, and UL documentation should be requested at quote time from the distributor."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL4106-7RC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL4106-7RC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}