{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL4115-8","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL4115-8","canonicalUrl":"https://aoctrl.com/siemens/5SL4115-8","factsUrl":"https://aoctrl.com/api/mcp/products/5SL4115-8","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL4115-8 miniature circuit breaker, 1-pole, D tripping characteristic, 1.6 A rated current, 10 kA breaking capacity, 400 V AC.","salesMarkdown":"The Siemens 5SL4115-8 is a SENTRON miniature circuit breaker (MCB) with a D tripping characteristic, rated 1.6 A at 400 V AC. It breaks fault currents up to 10 kA per EN 60898 and IEC 60947-2, covering residential and infrastructure branch circuits where inrush from small transformers or motor starters would nuisance-trip a C-curve. ## D-curve tripping and temperature derating The D characteristic means the magnetic trip fires at 10–20× In (16–32 A), so it holds through the high inrush of small power supplies, solenoid valves, or lighting ballasts without nuisance opening. Thermal derating is published: 1.6 A at 30 °C, 1.54 A at 40 °C, 1.5 A at 45 °C, and 1.43 A at 55 °C — factor that into the load calculation if the panel runs warm. Mounts in any position on a DIN rail; depth is 76 mm, height 90 mm, width 18 mm (one modular unit). Rated for overvoltage category III, pollution degree 2, and ambient temperature from -40 °C to 75 °C.","metaTitle":"Siemens 5SL4115-8 SENTRON MCB, 1.6 A, D Curve, 10 kA, 1P","metaDescription":"Siemens 5SL4115-8 SENTRON miniature circuit breaker, 1.6 A, D tripping characteristic, 10 kA breaking capacity per EN 60898 & IEC 60947-2, 1-pole, 400 V AC. Active production, avai","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"1","Width":"18 mm","Height":"90 mm","IP Rating":"IP20","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d4bebc237fa092287aaa2ed9f79819e0.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=206372&mlfb=5SL4115-8","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL4115-8/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL4115-8","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL4115-8 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}