{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL4202-8CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL4202-8CC","canonicalUrl":"https://aoctrl.com/siemens/5SL4202-8CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL4202-8CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL miniature circuit breaker, 5SL4202-8CC, 2-pole D-curve, 2 A, 400 V AC, 10 kA breaking capacity.","salesMarkdown":"The Siemens 5SL4202-8CC is a SENTRON 5SL series miniature circuit breaker rated for 2 A at 400 V AC with a D tripping characteristic and a 10 kA breaking capacity per EN 60898. Two-pole configuration, so it switches both phase and neutral in single-phase circuits or two phases in multi-phase applications up to 440 V. Mounts in any position — no derating for orientation. IP20 with conductors connected, so it's enclosed in a distribution board or panel; not rated for wet environments. Sealable with a lead or tag for tamper-proof installations. Neutral conductor not switched — this is a 2P breaker that does not break the neutral internally; verify your circuit design if neutral isolation is required.","metaTitle":"Siemens 5SL4202-8CC SENTRON MCB, 2-pole D 2A 400V 10kA","metaDescription":"Siemens 5SL4202-8CC SENTRON miniature circuit breaker, 2-pole, D-curve, 2 A, 400 V AC, 10 kA breaking capacity. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Rated Value":"50 Hz","Halogen-Free":"Yes","Silicon-Free":"Yes","Number of poles":"2","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Degree of pollution":"2","Product designation":"Miniature circuit breaker","Protection class IP":"IP20, with connected conductors","Overvoltage category":"3","Design of the product":"5SL miniature circuit breakers","Number of width units":"2","Number of poles / Note":"2P","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SL4CC","Suitability for operation":"Residential buildings/infrastructure","Tripping characteristic class":"D","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"10 kA","Product feature / Touch protection":"Yes","Supply voltage / at AC / rated value":"400 V","Operating current / at AC / rated value":"2 A","Influence of the surrounding temperature":"+55 °C, max. 95% humidity","Vibration resistance / acc. to IEC 60068-2-6":"50 m/s² at 25 to 150 Hz","with multi-phase operation / at AC / maximum":"440 V","Product function / neutral conductor switching":"No","with multi-phase operation / at AC / rated value":"440 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7404ae85aaaa1f58b9c29459ca8938a8.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=62670&mlfb=5SL4202-8CC","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL4202-8CC/alternatives.json"},"ai":{"faq":[{"question":"What is 5SL4202-8CC used for?","answer":"It is a 2-pole D-curve miniature circuit breaker rated 2 A at 400 V AC with 10 kA breaking capacity. The D-curve suits loads with high inrush current — small motors, transformers, discharge lighting — in residential and infrastructure panels."},{"question":"Where can I buy 5SL4202-8CC?","answer":"Sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — no online stock or price published."},{"question":"What compliance documentation does 5SL4202-8CC carry?","answer":"The part is rated per EN 60898 for breaking capacity and carries Siemens SENTRON approvals. Specific RoHS, REACH, UL, and IEC declarations are available from Siemens directly; the product is designed for residential and infrastructure use per its specification."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL4202-8CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL4202-8CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}