{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL4215-8","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL4215-8","canonicalUrl":"https://aoctrl.com/siemens/5SL4215-8","factsUrl":"https://aoctrl.com/api/mcp/products/5SL4215-8","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL4 series, miniature circuit breaker, 2-pole, D characteristic, 1.6 A rated current, 10 kA breaking capacity per EN 60898.","salesMarkdown":"The D curve holds through a 10–20× rated-current surge, so it clears only on a hard fault, not a normal load transient. The D characteristic (tripping between 10× and 20× In) is the key selection parameter here. At 1.6 A, that means the magnetic trip fires between 16 A and 32 A — enough headroom for a small motor or a bank of LED drivers without nuisance trips. But the thermal element still protects the downstream cable at the continuous rating. Temperature derating is real on this part. The 1.6 A rating holds at 30 °C; at 40 °C it drops to 1.54 A, at 45 °C to 1.5 A, and at 55 °C to 1.43 A. The MCB is rated for ambient up to 55 °C with 95% humidity, so it's fine in a damp basement or outdoor-rated enclosure as long as the IP20 (with connected conductors) is respected. Multi-phase operation is rated at 400/440 V AC; single-phase supply voltage is 400 V AC. The DC rating maxes at 72 V, so this is an AC-primary breaker — don't spec it for a DC distribution bus above that. ## Mechanical and panel fit Height is 90 mm. Mounting position is any, so you can lay it sideways in a shallow enclosure if the DIN rail is oriented horizontally. It's sealable (tamper-evident seal wire can be threaded through the housing), halogen-free and silicon-free — important for clean-room or corrosive-environment panels where outgassing matters. Touch protection is built in; neutral conductor switching is not included (this is a 2-pole breaker that switches both phase conductors but does not break the neutral — verify your circuit topology). For a daily-switched load, consider a contactor or a dedicated switch-disconnector instead.","metaTitle":"Siemens 5SL4215-8 SENTRON MCB, D Curve, 2-Pole, 1.6 A, 10 kA","metaDescription":"Siemens 5SL4215-8 SENTRON miniature circuit breaker, D tripping characteristic, 2-pole, 1.6 A rated, 10 kA breaking capacity per EN 60898. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"2","Width":"36 mm","Height":"90 mm","IP Rating":"IP20","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f4ab5c3772864a9cd57ddebfe9666c12.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=369457&mlfb=5SL4215-8","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL4215-8/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL4215-8","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL4215-8 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}