{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL4410-0RC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL4410-0RC","canonicalUrl":"https://aoctrl.com/siemens/5SL4410-0RC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL4410-0RC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens Betagard 5SL4410-0RC, miniature circuit breaker, 10 A, 4-pole, Z characteristic, 10 kA breaking capacity per EN 60898.","salesMarkdown":"The 5SL4410-0RC is a Siemens Betagard miniature circuit breaker rated 10 A at 415 V AC, 4-pole, with a Z tripping characteristic and 10 kA breaking capacity per EN 60898. The Z curve trips between 2 and 3 times rated current — designed for semiconductor or sensitive electronic loads where standard B/C curves would nuisance-trip on inrush. ## Temperature derating and environmental limits Rated current holds at 10 A up to 50 °C ambient; above that, derate linearly to 9.5 A at 60 °C. The breaker operates from -40 to 75 °C, storage included, so it handles unheated electrical rooms or outdoor enclosures. Snap-on DIN rail mount, any position. Installation depth 70 mm behind the panel surface; overall depth 76 mm includes the front toggle. Sealable with a lead seal or adhesive label for LOTO compliance. Halogen-free and silicon-free construction, suitable for clean-room or marine environments where outgassing is restricted.","metaTitle":"Siemens Betagard 5SL4410-0RC MCB, 10A 4P Z-Char 10kA","metaDescription":"Siemens Betagard 5SL4410-0RC miniature circuit breaker, 10A, 4-pole, Z characteristic, 10kA per EN 60898. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SL4410-0RC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature Circuit Breaker 10A 4-pole Z characteristic 10kA","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"4P","Number Of Poles":"4","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"Betagard","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"10 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","acc. to DIN EN 61346-2":"F","at 30 °C / rated value":"10.9 A","at 40 °C / rated value":"10.5 A","at 45 °C / rated value":"10.2 A","at 50 °C / rated value":"10 A","at 55 °C / rated value":"9.8 A","at 60 °C / rated value":"9.5 A","Number Of Modular Width Units":"4","Tripping Characteristic Class":"Z","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"10 kA","Product Feature / Touch Protection":"Yes","supply voltage / at AC / rated value":"415 V","Type Of Voltage / Of The Operating Voltage":"AC","vibration resistance / acc. to IEC 60068-2-6":"50 m/s² at 25 to 150 Hz","with multi-phase operation / at AC / maximum":"440 V","Product Component / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","with single-phase operation / at AC / rated value":"440 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad43b931801eb24b98c90e7f6e2824ba.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1502390&mlfb=5SL4410-0RC"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SL4410-0RC?","answer":"Submit an RFQ through this listing. The part is sourced to order via independent distribution; availability and price are confirmed at quote time."},{"question":"What is 5SL4410-0RC's listed depth and width?","answer":"Depth is 76 mm, width is 72 mm (4 modular units). Installation depth behind the panel is 70 mm."},{"question":"Will 5SL4410-0RC drop into a panel specified around 5SL3116-6MB?","answer":"Both are 4-pole DIN-rail MCBs, but 5SL3116-6MB is a 16 A B-curve unit. The 5SL4410-0RC is 10 A Z-curve — same footprint (4 MW), but the Z curve trips faster on low overcurrents. Check the load's inrush profile before swapping; the physical fit is identical."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL4410-0RC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL4410-0RC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}