{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL4501-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL4501-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SL4501-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL4501-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL4501-7CC miniature circuit breaker, 1-pole+N, 230 V AC, 1 A, C characteristic, 10 kA breaking capacity per EN 60898, 2 width units (36 mm), IP20 with connected conductors.","salesMarkdown":"The Siemens 5SL4501-7CC is a SENTRON 5SL miniature circuit breaker, 1-pole+N, rated 1 A at 230 V AC with a C tripping characteristic and a 10 kA breaking capacity per EN 60898. DIN-rail snap-on, any mounting position. Terminal accepts 0.75–25 mm² solid or stranded copper — the 25 mm² upper end is generous for a 1 A breaker, but useful when you're looping feed-through conductors from a larger upstream device. IP20 with conductors connected — fine for enclosed panels; keep it behind a locked door or gland plate.","metaTitle":"Siemens 5SL4501-7CC SENTRON MCB, 1P+N, C-curve, 1 A, 10 kA","metaDescription":"Siemens 5SL4501-7CC SENTRON miniature circuit breaker, 1-pole+N, 230 V AC, 1 A, C characteristic, 10 kA breaking capacity per EN 60898. Current lifecycle stage, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Solid":"0.75 ... 25 mm²","Width":"36 mm","title":"5SL4501-7CC","Height":"90 mm","Sealable":"Yes","Stranded":"0.75 ... 25 mm²","Rated Value":"50 Hz","description":"Miniature circuit breaker 230 V 10kA, 1+N-pole, C, 1 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Wertebereich":"-25 ... +55 °C","Number of poles":"2","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Ambient temperature":"-40 ... +75 °C","Product designation":"Miniature circuit breaker","Protection class IP":"IP20, with connected conductors","Overvoltage category":"3","Design of the product":"5SL miniature circuit breakers","Energy limiting class":"3","Number of width units":"2","Number of poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SL4CC","Suitability for operation":"Residential buildings/infrastructure","Current / at AC / rated value":"1 A","Tripping characteristic class":"C","acc. to EN 60898 / rated value":"10 kA","Product feature / Touch protection":"Yes","Supply voltage / at AC / rated value":"230 V","Influence of the surrounding temperature":"+55 °C, max. 95% humidity","Vibration resistance / acc. to IEC 60068-2-6":"50 m/s² at 25 to 150 Hz","Tightening torque / with screw-type terminals":"2.5 ... 3 N·m","Product function / neutral conductor switching":"Yes","with single-phase operation / at AC / rated value":"250 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3ce392804f2af16e298b4cc6cab875e3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=8790&mlfb=5SL4501-7CC"},"ai":{"faq":[{"question":"Where can I buy 5SL4501-7CC and get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability."},{"question":"What is the breaking capacity of 5SL4501-7CC?","answer":"10 kA per EN 60898 at 230 V AC, which covers most residential and light commercial distribution board fault levels."},{"question":"What conductor sizes does 5SL4501-7CC accept?","answer":"Solid or stranded copper from 0.75 mm² up to 25 mm². The 25 mm² top end is generous for a 1 A breaker, good for looping feed-through conductors."},{"question":"What is the depth of 5SL4501-7CC?","answer":"76 mm overall depth; installation depth behind the panel face is 70 mm."},{"question":"Will 5SL4501-7CC drop into a panel specified around 5SL6563-7BB without rewiring?","answer":"Both are SENTRON 5SL series MCBs with the same DIN-rail footprint and 2 width units (36 mm), so physical fit is the same. Verify the rating and tripping characteristic match your circuit — 5SL4501-7CC is 1 A C-curve 1P+N; the 5SL6563-7BB is a different rating and poles."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL4501-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL4501-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}