{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL4510-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL4510-6","canonicalUrl":"https://aoctrl.com/siemens/5SL4510-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SL4510-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL4510-6, miniature circuit breaker, 1P+N, B characteristic, 10 A rated, 10 kA breaking capacity, 230 V AC, 2 MW.","salesMarkdown":"## Pole configuration and panel fit This is a 1P+N (2-pole) design — the switched phase plus a switched neutral — in a 36 mm wide housing occupying 2 modular width units on a DIN rail. The neutral pole opens and closes with the phase, which is required by some national wiring rules for final sub-circuits. Rated 10 kA at 230 V AC per EN 60898 and IEC 60947-2, the 5SL4510-6 coordinates cleanly with a 25 kA upstream main breaker in most residential and light commercial panels. For motor or transformer circuits with higher inrush, a C-curve sibling would be the better call. ## Environmental range and approvals IP20 with connected conductors, so it requires enclosure protection against moisture ingress.","metaTitle":"Siemens 5SL4510-6 SENTRON MCB, 1P+N, B Curve, 10 A, 10 kA","metaDescription":"Siemens 5SL4510-6 SENTRON miniature circuit breaker, 1P+N, B characteristic, 10 A, 10 kA breaking capacity per EN 60898. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SL4510-6","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 230 V 10kA, 1+N-pole, B, 10 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","Suitability For Operation":"Residential buildings/infrastructure","at DC rated value maximum":"72 V","Number Of Modular Width Units":"2","Tripping Characteristic Class":"B","supply voltage at AC rated value":"230 V","according to EN 60898 rated value":"10 kA","according to IEC 60947-2 rated value":"10 kA","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50/60 Hz","with single-phase operation at AC rated value":"250 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.9 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2b1f818a90e491367580c0983a12fa48.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=373569&mlfb=5SL4510-6"},"ai":{"faq":[{"question":"What is the breaking capacity of the 5SL4510-6?","answer":"The 5SL4510-6 is rated 10 kA breaking capacity per both EN 60898 and IEC 60947-2 at 230 V AC."},{"question":"What is the difference between the 5SL4510-6 and the 5SL4363-7?","answer":"The 5SL4363-7 is a 3-pole (3P) C-curve MCB rated 63 A in a 54 mm (3 MW) housing, while the 5SL4510-6 is a 1P+N B-curve 10 A unit in a 36 mm (2 MW) housing. They share the same 10 kA breaking capacity and SENTRON series construction, but differ in poles, curve, current rating, and width — they are not drop-in replacements."},{"question":"Where can I buy the 5SL4510-6?","answer":"The 5SL4510-6 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL4510-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL4510-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}