{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL4563-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL4563-7","canonicalUrl":"https://aoctrl.com/siemens/5SL4563-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SL4563-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL4563-7 miniature circuit breaker, 1P+N, C-curve, 63 A, 10 kA breaking capacity per EN 60898, 230 V AC, 2 MW.","salesMarkdown":"## Siemens 5SL4563-7 SENTRON MCB — 63 A, C-Curve, 1P+N At 40 °C ambient the continuous rating derates to 59.67 A; at 55 °C it drops to 54.29 A — factor that into the branch-circuit load calculation if the panel runs warm. The neutral pole switches with the line (1P+N, not 2P), so the neutral is opened and closed together with the phase. That matters for isolation — you get full disconnection on both conductors, not just the phase. Mounting position is unrestricted, so it can be installed horizontally or vertically without derating the current. For frequent switching as a load-break device, consider a contactor instead.","metaTitle":"Siemens 5SL4563-7 SENTRON MCB, 1P+N, C-Curve, 63 A, 10 kA","metaDescription":"Siemens 5SL4563-7 SENTRON miniature circuit breaker, 1P+N, 63 A, C-curve, 10 kA breaking capacity per EN 60898. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","at AC / rated value":"63 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","according to EN 61346-2":"F","at 30 °C / rated value":"63 A","at 40 °C / rated value":"59.67 A","at 45 °C / rated value":"57.96 A","at 55 °C / rated value":"54.29 A","according to IEC 81346-2":"F","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","at DC / rated value / maximum":"72 V","Product Feature / Touch Protection":"Yes","according to EN 60898 / rated value":"10 kA","supply voltage / at AC / rated value":"230 V","according to IEC 60947-2 / rated value":"10 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","with single-phase operation / at AC / rated value":"250 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/002ad75c44964f6a2bceabbd53078d85.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=537964&mlfb=5SL4563-7","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL4563-7/alternatives.json"},"ai":{"faq":[{"question":"Does the 5SL4563-7 switch the neutral?","answer":"Yes, the 1P+N configuration switches both the phase and neutral conductors together, providing full disconnection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL4563-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL4563-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}