{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL4608-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL4608-6","canonicalUrl":"https://aoctrl.com/siemens/5SL4608-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SL4608-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL4 series, 5SL4608-6 miniature circuit breaker, 4-pole 3P+N, 8 A, B characteristic, 10 kA breaking capacity, 400 V AC.","salesMarkdown":"The Siemens 5SL4608-6 is a SENTRON 5SL4 series miniature circuit breaker — a 4-pole (3P+N) unit rated 8 A with a B tripping characteristic and a 10 kA breaking capacity per EN 60898 and IEC 60947-2. It's designed for residential and infrastructure branch-circuit protection, switching the neutral conductor as well as the three phases. The 4-pole body occupies 4 width units (72 mm wide, 90 mm tall, 76 mm deep with 70 mm installation depth). Screw terminals accept solid or stranded conductors from 0.75 to 25 mm²; tighten to 2.5–3 N·m. IP20 with connected conductors. Overvoltage category 3, energy limiting class 3.","metaTitle":"Siemens 5SL4608-6 SENTRON MCB, 4-pole 8A B-curve, 10kA","metaDescription":"Siemens 5SL4608-6 SENTRON miniature circuit breaker, 4-pole (3P+N), 8 A rated, B tripping characteristic, 10 kA breaking capacity per EN 60898. Current lifecycle stage. Available t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"76 mm","Solid":"0.75 ... 25 mm²","Width":"72 mm","Height":"90 mm","Sealable":"Yes","Stranded":"0.75 ... 25 mm²","Rated Value":"50 Hz","Halogen-Free":"Yes","Silicon-Free":"Yes","Wertebereich":"-25 ... +55 °C","Number of poles":"4","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Ambient temperature":"-40 ... +75 °C","Product designation":"Miniature circuit breaker","Protection class IP":"IP20, with connected conductors","Overvoltage category":"3","Design of the product":"5SL miniature circuit breakers","Energy limiting class":"3","Number of width units":"4","Number of poles / Note":"3P+N","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SL4","Suitability for operation":"Residential buildings/infrastructure","Current / at AC / rated value":"8 A","Tripping characteristic class":"B","at DC / rated value / maximum":"60 V","acc. to EN 60898 / rated value":"10 kA","acc. to IEC 60947-2 / rated value":"10 kA","Product feature / Touch protection":"Yes","Supply voltage / at AC / rated value":"400 V","Influence of the surrounding temperature":"+55 °C, max. 95% humidity","with multi-phase operation / at AC / maximum":"440 V","Tightening torque / with screw-type terminals":"2.5 ... 3 N·m","Product function / neutral conductor switching":"Yes","with multi-phase operation / at AC / rated value":"440 V","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fe0607c969e3cb56ae4acad7134d99c5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=407789&mlfb=5SL4608-6","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL4608-6/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SL4608-6?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."},{"question":"What is the breaking capacity of 5SL4608-6?","answer":"10 kA rated breaking capacity per both EN 60898 and IEC 60947-2 at 400 V AC."},{"question":"What wire sizes does 5SL4608-6 accept?","answer":"Screw terminals accept solid or stranded conductors from 0.75 to 25 mm²."},{"question":"Does 5SL4608-6 switch the neutral?","answer":"Yes, it is a 3P+N design that switches the neutral conductor along with the three phases."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL4608-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL4608-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}