{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL4610-8","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL4610-8","canonicalUrl":"https://aoctrl.com/siemens/5SL4610-8","factsUrl":"https://aoctrl.com/api/mcp/products/5SL4610-8","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL4610-8, 4-pole miniature circuit breaker, D tripping characteristic, 10 A rated current at 30 °C, 10 kA breaking capacity per EN 60898 and IEC 60947-2, 400 V AC supply voltage, 4 modular width units.","salesMarkdown":"## What the ratings mean for fit The 5SL4610-8 is a 4-pole (3P+N) miniature circuit breaker from the SENTRON family, with a D tripping characteristic rated 10 A at 30 °C. The D curve means it tolerates high inrush currents — typical for motor, transformer, or lighting ballast loads — without nuisance tripping. Breaking capacity is 10 kA per both EN 60898 and IEC 60947-2, so it safely clears faults up to that level in residential or light commercial infrastructure panels. The 400 V AC supply rating and 440 V AC multi-phase maximum match standard three-phase distribution. Thermal derating is published: 9.24 A at 40 °C, 8.8 A at 45 °C, and 7.96 A at 55 °C. If the panel ambient runs hot, size the load accordingly — the 10 A nameplate is only valid at 30 °C. The breaker is IP20 with connected conductors, so it's intended for enclosed distribution boards, not wet or dusty environments. ## Panel integration notes Snap-on DIN rail mount, any position. Occupies 4 modular width units (72 mm wide, 90 mm tall, 76 mm deep, 70 mm installation depth). The sealable housing is halogen-free and silicon-free, which matters for panels in environments sensitive to outgassing — food processing, medical, or telecom shelters. Touch protection is built in. ## Compliance and documentation Rated for overvoltage category III, pollution degree 2, energy limitation class 3. The neutral conductor is switched (3P+N). Mechanical service life is 10 000 operating cycles typical. The part carries IEC and EN markings for the listed breaking capacities; compliance documentation (RoHS, REACH, UL, IEC) is provided by Siemens with the product.","metaTitle":"Siemens 5SL4610-8 SENTRON MCB, 4P D-10 A, 10 kA","metaDescription":"Siemens 5SL4610-8 SENTRON miniature circuit breaker, 4-pole D-curve 10 A, 10 kA breaking capacity per EN 60898 / IEC 60947-2. Active lifecycle, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SL4610-8","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 10kA, 3+N-pole, D, 10 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"4","Type Of Voltage":"AC","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"10 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Number Of Poles / Note":"3P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 30 °C / rated value":"10 A","at 40 °C / rated value":"9.24 A","at 45 °C / rated value":"8.8 A","at 55 °C / rated value":"7.96 A","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"4","Tripping Characteristic Class":"D","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"10 kA","acc. to IEC 60947-2 / rated value":"10 kA","Product Feature / Touch Protection":"Yes","supply voltage / at AC / rated value":"400 V","Influence Of The Surrounding Temperature":"+55 °C, max. 95% humidity","with multi-phase operation / at AC / maximum":"440 V","Product Function / Neutral Conductor Switching":"Yes","with multi-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c10d9f3167db9ac5897614c07c49f6bf.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=337841&mlfb=5SL4610-8"},"ai":{"faq":[{"question":"Where can I buy 5SL4610-8 and how do I get a price?","answer":"The 5SL4610-8 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is 5SL4610-8's listed depth (76 mm) on this component line?","answer":"The 5SL4610-8 has a depth of 76 mm, with an installation depth of 70 mm. Width is 72 mm (4 modular units), height is 90 mm."},{"question":"What compliance documentation does this brand provide for 5SL4610-8 (RoHS, REACH, UL, IEC)?","answer":"Siemens provides RoHS, REACH, UL, and IEC compliance documentation for the 5SL4610-8. The part carries IEC and EN markings for its 10 kA breaking capacity and is rated for overvoltage category III, pollution degree 2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL4610-8","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL4610-8 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}