{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL4613-8","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL4613-8","canonicalUrl":"https://aoctrl.com/siemens/5SL4613-8","factsUrl":"https://aoctrl.com/api/mcp/products/5SL4613-8","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL4613-8 miniature circuit breaker, 4-pole (3P+N), D characteristic, 13 A at 30 °C, 10 kA breaking capacity per IEC 60898, 400 V AC, IP20.","salesMarkdown":"The Siemens 5SL4613-8 is a SENTRON miniature circuit breaker (MCB) with a D tripping characteristic, four poles configured as 3P+N, and a rated current of 13 A at 30 °C. Breaking capacity is 10 kA per both IEC 60898 and IEC 60947-2, so it clears faults up to that level without upstream coordination issues in a residential or light-industrial distribution board. The 13 A rating derates with ambient temperature: 12.01 A at 40 °C, 11.44 A at 45 °C, and 10.35 A at 55 °C. The neutral conductor is switched (3P+N), which is required in some regional wiring codes to ensure the neutral is disconnected when the breaker is off. Touch protection is built in; It occupies 4 modular width units (72 mm wide), with a depth of 76 mm and an installation depth of 70 mm. The 90 mm height keeps it within a standard consumer unit or sub-distribution board. Sealable design allows lockout-tagout in industrial or infrastructure panels. Rated for ambient temperatures from -40 °C to 75 °C, with up to 95% humidity at 55 °C. That range covers unheated electrical rooms in cold climates and warm enclosures near process equipment.","metaTitle":"Siemens 5SL4613-8 SENTRON MCB, D Curve, 4-Pole, 13 A, 10 kA","metaDescription":"Siemens 5SL4613-8 SENTRON miniature circuit breaker, 4-pole (3P+N), D tripping characteristic, 13 A rated at 30 °C, 10 kA breaking capacity per IEC 60898. Current production, sourc","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SL4613-8","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 10kA, 3+N-pole, D, 13A","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"4","Type Of Voltage":"AC","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"13 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Number Of Poles / Note":"3P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 30 °C / rated value":"13 A","at 40 °C / rated value":"12.01 A","at 45 °C / rated value":"11.44 A","at 55 °C / rated value":"10.35 A","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"4","Tripping Characteristic Class":"D","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"10 kA","acc. to IEC 60947-2 / rated value":"10 kA","Product Feature / Touch Protection":"Yes","supply voltage / at AC / rated value":"400 V","Influence Of The Surrounding Temperature":"+55 °C, max. 95% humidity","with multi-phase operation / at AC / maximum":"440 V","Product Function / Neutral Conductor Switching":"Yes","with multi-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c10d9f3167db9ac5897614c07c49f6bf.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=287299&mlfb=5SL4613-8"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SL4613-8?","answer":"Pricing and stock are confirmed at quote time. Submit an RFQ through this listing; the sourcing desk will return current availability and a firm price for your quantity."},{"question":"Will 5SL4613-8 drop into a panel that was specified around 5SL4120-7CC without rewiring?","answer":"Both are 4-pole SENTRON MCBs with the same 72 mm width and DIN-rail mounting, so the mechanical fit is identical. The key difference is the tripping characteristic: the 5SL4120-7CC uses a B curve (for resistive/light loads), while the 5SL4613-8 uses a D curve (for high-inrush loads). If the panel was designed for a B-curve breaker, swapping to a D curve changes the protection coordination — verify the load type and upstream selectivity before substituting."},{"question":"What compliance documentation does this brand provide for 5SL4613-8 (RoHS, REACH, UL, IEC)?","answer":"The breaker is designed to IEC 60898 and IEC 60947-2, with a 10 kA breaking capacity under both standards. The SENTRON series typically carries CE marking and RoHS compliance; specific UL or REACH documentation should be verified against the manufacturer's current declarations for this order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL4613-8","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL4613-8 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}