{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL5106-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL5106-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SL5106-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL5106-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL5106-7CC, miniature circuit breaker, 1-pole, C6, 125 V DC, 10 kA, IP20, 1 MW.","salesMarkdown":"The Siemens SENTRON 5SL5106-7CC is a 1-pole miniature circuit breaker (MCB) with a C6 tripping characteristic, rated for 125 V DC and a breaking capacity of 10 kA. The C6 curve means the breaker trips at 5 to 10 times rated current (30–60 A magnetic trip), which is standard for moderate inrush loads like lighting or control transformers on a DC bus. The 125 V DC rating is the maximum operating voltage — verify your system voltage stays under that. The 10 kA interrupting rating at 125 V DC tells you it can safely clear a fault up to 10,000 amps without welding contacts or cascading upstream; that's a solid figure for a 1-MW DC sub-panel. Its 18 mm width (1 MW) leaves room for adjacent modules in a crowded enclosure. The sealable feature allows lockout/tagout for maintenance isolation.","metaTitle":"Siemens 5SL5106-7CC SENTRON MCB, 1P C6, 125 V DC, 10 kA","metaDescription":"Siemens SENTRON 5SL5106-7CC miniature circuit breaker, 1-pole C6, 125 V DC rated, 10 kA breaking capacity. IP20, 1 MW. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL5106-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit-breaker 125 V DC DC 10 kA 1-pole C6","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Suitability For Operation":"Residential buildings/infrastructure","at DC rated value maximum":"72 V","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","Type Of Voltage Of The Operating Voltage":"DC","Product Extension Installable Supplementary Devices":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b7cbc0e402056aee1f73e226063ca1aa.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=694673&mlfb=5SL5106-7CC"},"ai":{"faq":[{"question":"What is 5SL5106-7CC used for?","answer":"It is a miniature circuit breaker for DC circuits up to 125 V, providing overcurrent and short-circuit protection in residential and infrastructure distribution boards."},{"question":"Where can I buy 5SL5106-7CC?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest functional second-source for 5SL5106-7CC?","answer":"The 5SY6006-7 is a SENTRON peer with the same C6 curve and 6 A rating, but it is an AC-rated MCB (250 V AC) and includes a switched neutral pole. It will not drop into a DC-rated circuit without verifying the voltage and polarity requirements."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL5106-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL5106-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}