{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL5216-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL5216-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SL5216-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL5216-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON miniature circuit breaker, 2-pole, tripping characteristic C, 16 A rated current, 10 kA breaking capacity at 72 V DC, order code 5SL5216-7CC.","salesMarkdown":"The Siemens 5SL5216-7CC is a SENTRON miniature circuit breaker — 2-pole, C-curve, rated 16 A with a 10 kA DC breaking capacity at 72 V DC. ## DC rating and the so-what This breaker is specced for DC only — 72 V DC maximum, 10 kA. That's not a typo; it's not rated for AC at all. If your line runs a 48 V DC control bus or a 60 V DC power supply bank, this is the right MCB. The 2-pole design (2P) means both poles switch simultaneously, so you get full isolation on both the positive and return sides. That's a requirement in many DC systems to avoid a floating ground fault. The IP20 rating (with conductors connected) is typical for enclosed panel gear — no washdown rating, so keep it inside the cabinet. Sealable, halogen-free, silicon-free — matters if you're in a food plant or a clean room where outgassing is a concern.","metaTitle":"Siemens 5SL5216-7CC SENTRON MCB, 2P C16, 10 kA DC","metaDescription":"Siemens SENTRON 5SL5216-7CC miniature circuit breaker, 2-pole, C-curve, 16 A, 10 kA DC at 72 V DC. Active production, sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SL5216-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit-breaker 250 V DC DC 10 kA 2-pole C16","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","at DC / rated value / maximum":"72 V","Type Of Voltage / Of The Operating Voltage":"DC"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bb3ee617aa74d6246a1034c2687f1b77.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=694703&mlfb=5SL5216-7CC"},"ai":{"faq":[{"question":"Where can I buy the 5SL5216-7CC and get a price?","answer":"We source and quote this part to order against an RFQ. Availability and current pricing are confirmed at quote time — submit a request and we'll get you a firm number."},{"question":"What is the depth of the 5SL5216-7CC?","answer":"The depth is 76 mm, with a 70 mm installation depth behind the panel face. That's standard for SENTRON 2-pole MCBs."},{"question":"Will the 5SL5216-7CC drop into a panel specified for the 5SL6220-7?","answer":"Same footprint — both are 36 mm wide, 90 mm tall, 76 mm deep, 2-pole SENTRON MCBs. The 5SL6220-7 is a 20 A AC-rated version; the 5SL5216-7CC is 16 A DC-rated. Mechanically they interchange without rewiring, but verify the voltage and current rating match your circuit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL5216-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL5216-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}