{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6002-7KL","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6002-7KL","canonicalUrl":"https://aoctrl.com/siemens/5SL6002-7KL","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6002-7KL","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6002-7KL miniature circuit breaker, C-curve, 2 A rated, 6 kA breaking capacity per EN 60898, 1 MW, 76 mm depth.","salesMarkdown":"## Integrator's terse spec recap The Siemens 5SL6002-7KL is a SENTRON miniature circuit breaker with a C-curve tripping characteristic, rated 2 A at AC. Its 6 kA breaking capacity per EN 60898 covers most residential and light commercial branch circuits. The 18 mm width (1 MW) snaps onto standard DIN rail, and the 76 mm depth fits shallow enclosures. Rated for overvoltage category III, pollution degree 2. ## What the ratings mean for fit The C-curve means the magnetic trip activates at 5–10× rated current — suited for moderate inrush loads like small motors or lighting ballasts. The 2 A rating at 30 °C derates to 1.92 A at 40 °C and 1.75 A at 60 °C; if the panel ambient runs hot, size up one frame. The 6 kA breaking capacity per EN 60898 certifies it for interrupting short-circuit faults up to that level without upstream damage in residential/infrastructure installations. ## Panel integration notes Snaps onto standard DIN rail in any mounting position. The 18 mm width occupies one modular unit — useful when filling a tight gland plate. Touch protection is built in. IP20 with connected conductors means it's for enclosed panels, not washdown zones. Vibration-resistant per IEC 60068-2-6.","metaTitle":"Siemens 5SL6002-7KL SENTRON MCB, C-Curve 2 A, 6 kA","metaDescription":"Siemens 5SL6002-7KL SENTRON miniature circuit breaker, 2 A C-curve, 6 kA per EN 60898, 1 MW. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL6002-7KL","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"CIRCUIT BREAKER 230V 6KA, 1+N-POLE/1MW, N LEFT C2","Halogen-Free":"Yes","Silicon-Free":"Yes","lifecycle_stage":"current","Fastening Method":"standard rail","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"2 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"No","Design Of The Product":"Miniature circuit breaker compact","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 30 °C / rated value":"2 A","at 40 °C / rated value":"1.92 A","at 45 °C / rated value":"1.88 A","at 50 °C / rated value":"1.84 A","at 55 °C / rated value":"1.79 A","at 60 °C / rated value":"1.75 A","Combined Terminal Bottom":"No","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"6 kA","Position / Of Power Supply Cord":"Any","Product Feature / Touch Protection":"Yes","Type Of Voltage / Of The Operating Voltage":"AC","vibration resistance / acc. to IEC 60068-2-6":"Yes","insulation voltage (Ui) / at AC / rated value":"250 V","with single-phase operation / at AC / maximum":"250 V","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"4 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3b6fe2a7c12f193fa59700ee28c21649.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1364775&mlfb=5SL6002-7KL"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SL6002-7KL?","answer":"The 5SL6002-7KL is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What is 5SL6002-7KL's depth?","answer":"The 5SL6002-7KL has a depth of 76 mm, which fits standard shallow enclosures. Installation depth is 70 mm."},{"question":"What compliance documentation does 5SL6002-7KL carry?","answer":"The 5SL6002-7KL is rated per EN 60898 for breaking capacity, carries overvoltage category III, pollution degree 2, and is halogen-free and silicon-free. It is designated for residential buildings/infrastructure."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6002-7KL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6002-7KL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}