{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6006-7MC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6006-7MC","canonicalUrl":"https://aoctrl.com/siemens/5SL6006-7MC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6006-7MC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6006-7MC, miniature circuit breaker COM compact, 1P+N, 6 A rated at AC, 16 A full-scale, 18 mm wide, 76 mm deep.","salesMarkdown":"## What this MCB carries The integrated ammeter, voltmeter, wattmeter, reactive-power meter, and frequency meter make this a metering MCB, not just a protective device. It complies with IEC/EN60898-1 and GB/T10963.1, pollution degree 2, overvoltage category III. Fastens onto standard DIN rail, any mounting position. Front face is IP40; rear side is IP20. ## Temperature derating and real-world current Rated 6 A at 30 °C and at AC. At 40 °C the continuous rating drops to 5.56 A; at 50 °C it's 4.81 A; at 60 °C it's 4.54 A. The 55 °C value (5.07 A) shows a slight non-monotonicity — likely a measurement point — but the trend is clear: above 40 °C derate by roughly 10% per 10 °C rise.","metaTitle":"Siemens 5SL6006-7MC SENTRON MCB, 6 A, 1P+N, COM Compact","metaDescription":"Siemens 5SL6006-7MC SENTRON miniature circuit breaker, 6 A rated, 1P+N, COM compact design. Current lifecycle. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL6006-7MC","Height":"90 mm","Ammeter":"Yes","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC/EN60898-1, GB/T10963.1","Rear Side":"IP20","Voltmeter":"Yes","Wattmeter":"Yes","For Shocks":"IEC 61373","description":"Miniature Circuit Breaker Measuring, Communication AC 230V 6kA, 1+N pole, C, 6A Please consider Radio approval! List of countries: see Certificates","Halogen-Free":"Yes","On The Front":"IP40","Silicon-Free":"Yes","Initial Value":"0.04 A","Design Of Pole":"1P+N","Frequency Meter":"Yes","lifecycle_stage":"current","Fastening Method":"standard rail","Full-Scale Value":"16 A","Mounting Position":"any","at AC rated value":"6 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Reactive Power Meter":"Yes","Combined Terminal Top":"No","Design Of The Product":"Miniature circuit breaker COM compact","Protocol Is Supported":"Wireless protocol","at 30 °C rated value":"6 A","at 40 °C rated value":"5.56 A","at 45 °C rated value":"5.32 A","at 50 °C rated value":"4.81 A","at 55 °C rated value":"5.07 A","at 60 °C rated value":"4.54 A","Energy Limitation Class":"3","according to EN 61346-2":"F","Combined Terminal Bottom":"No","according to IEC 81346-2":"F","Suitability For Operation":"Residential buildings/infrastructure","Standards For Error Limits":"based on IEC61557-12, IEC62053-22, IEC62053-23","Neutral Conductor Switching":"Yes","For Measured Variable Current":"0.5 %","For Measured Variable Voltage":"0.5 %","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","Type Of Measured Value Detection":"completely","according to EN 60898 rated value":"6 kA","For Measured Variable Active Power":"1 %","Status Display Of The Measured Data":"voltage, current, active power, apparent power, reactive power, active energy, line frequency, power factor, temperature, switching cycles, operating hours, tripping, warnings","Ambient Temperature During Operation":"-25...45°C: max. 85%rF, 45 60°C: max. 43%rF","For Measured Variable Apparent Power":"1 %","For Measured Variable Reactive Power":"1 %","Guideline Via Radio-Controlled System":"2014/53/EU","For Measured Variable Electrical Energy":"1 %","Measurable Line Frequency Initial Value":"45 Hz","Type Of Voltage Of The Operating Voltage":"AC","Frequency With Radio Transmission Maximum":"2 483.5 MHz","Frequency With Radio Transmission Minimum":"2 400 MHz","Reference Condition For Metering Accuracy":"according IEC61557-12, IEC62053-22 and IEC62053-23","insulation voltage (Ui) at AC rated value":"250 V","with single-phase operation at AC maximum":"250 V","Measurable Line Frequency Full-Scale Value":"65 Hz","Measuring Category For Voltage Measurement":"CATIII according IEC 61010-2-030","Measuring Procedure For Current Measurement":"TRMS","Measuring Procedure For Voltage Measurement":"TRMS","Value Range Of The Supply Voltage Frequency":"50/60 Hz","reference current (Iref) 1 at AC rated value":"6 A","Apparent Power Consumption Of The Power Supply":"0.4 VA","For Environmental Sinusoidal Oscillation Check":"IEC 60068-2-6","vibration resistance according to IEC 60068-2-6":"Yes","Mechanical Service Life (Switching Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","electrical endurance (switching cycles) at AC load in the mean value":"7 500","power loss [W] for rated value of the current at AC in hot operating state per pole":"0.9 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3b6fe2a7c12f193fa59700ee28c21649.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1438018&mlfb=5SL6006-7MC"},"ai":{"faq":[{"question":"What is the width and depth of 5SL6006-7MC?","answer":"Width is 18 mm (one module), depth is 76 mm, installation depth 70 mm. Mounts on standard DIN rail."},{"question":"Will 5SL6006-7MC drop into a panel specified around 5SL6120-7?","answer":"Both are SENTRON COM compact MCBs with the same 18 mm width and DIN-rail mount, so the mechanical fit is the same. The difference is electrical: 5SL6006-7MC is 6 A rated, 1P+N; 5SL6120-7 is a different rating variant. Check the circuit's ampacity before swapping."},{"question":"What compliance documentation is available for 5SL6006-7MC?","answer":"The MCB is certified to IEC/EN60898-1 and GB/T10963.1. It is halogen-free and silicon-free. Pollution degree 2, overvoltage category III. Shock-rated per IEC 61373 for rail applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6006-7MC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6006-7MC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}