{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6113-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6113-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SL6113-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6113-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL series, miniature circuit breaker (MCB), 1-pole, C-curve, 13 A, 6 kA breaking capacity per EN 60898, 400 V AC, 1 width unit (18 mm).","salesMarkdown":"The Siemens 5SL6113-7CC is a SENTRON 5SL-series miniature circuit breaker — one pole, C-curve trip characteristic, rated 13 A at 400 V AC, with a 6 kA breaking capacity tested to EN 60898. The C-curve (tripping characteristic class C) means it holds 5–10× rated current for short overloads — designed for inductive loads like small motors, fluorescent lighting, and transformer inrush where a B-curve would nuisance-trip. The 72 V DC maximum rating covers control-circuit applications. ## Where it goes — deployment context Sized for residential and infrastructure distribution boards — the 5SL series is a standard DIN-rail MCB line for Siemens SENTRON panels. Energy limiting class 3 means it restricts let-through energy under fault conditions — helps downstream coordination and reduces arc-flash energy at the panel. Ambient temperature range -40 to 75 °C, with periodic exposure to +55 °C at 95% humidity — suitable for outdoor enclosures or unconditioned electrical rooms.","metaTitle":"Siemens 5SL6113-7CC SENTRON MCB, 1P C 13A, 6kA","metaDescription":"Siemens SENTRON 5SL6113-7CC miniature circuit breaker, 1-pole, C-curve, 13 A, 6 kA breaking capacity per EN 60898, 400 V AC. Current lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL6113-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Rated Value":"50 Hz","description":"Miniature circuit breaker 230/400 V 6kA, 1-pole, C, 13A Circuit breaker 230/400 V 6kA, 1-pole, C, 13A","Halogen-Free":"Yes","Silicon-Free":"Yes","Number of poles":"1","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Degree of pollution":"2","Product designation":"Miniature circuit breaker","Protection class IP":"IP20, with connected conductors","Overvoltage category":"3","Design of the product":"5SL miniature circuit breakers","Energy limiting class":"3","Number of width units":"1","Number of poles / Note":"1P","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SL6CC","Suitability for operation":"Residential buildings/infrastructure","Current / at AC / rated value":"13 A","Tripping characteristic class":"C","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"6 kA","Product feature / Touch protection":"Yes","Supply voltage / at AC / rated value":"400 V","Influence of the surrounding temperature":"Periodically +55°C, max. 95% humidity","Vibration resistance / acc. to IEC 60068-2-6":"50 m/s² at 25 to 150 Hz","with multi-phase operation / at AC / maximum":"440 V","Product function / neutral conductor switching":"No","with multi-phase operation / at AC / rated value":"440 V","with single-phase operation / at AC / rated value":"250 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/448c45311fe75ee70c38c3b99456851d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=163920&mlfb=5SL6113-7CC"},"ai":{"faq":[{"question":"Will the 5SL6113-7CC drop into a panel specified for a 5SL6132-6MB?","answer":"Both are 1-pole SENTRON 5SL-series MCBs on the same 18 mm DIN-rail footprint, so mechanical fit is identical. The difference is electrical: the 5SL6113-7CC is a 13 A C-curve, while the 5SL6132-6MB carries a different rating and curve — verify the branch circuit protection requirements before substitution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6113-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6113-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}