{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6114-7BB","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6114-7BB","canonicalUrl":"https://aoctrl.com/siemens/5SL6114-7BB","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6114-7BB","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6 series, 5SL6114-7BB miniature circuit breaker, 1-pole, rated current 0.3 A, C characteristic, breaking capacity 6 kA, 400 V AC.","salesMarkdown":"## What this 0.3 A C-curve MCB is for The Siemens 5SL6114-7BB is a 1-pole SENTRON miniature circuit breaker rated 0.3 A at 400 V AC, with a C tripping characteristic and a 6 kA breaking capacity per EN 60898 and IEC 60947-2. That 0.3 A rating is unusually low — it is sized for protecting control transformers, signal circuits, or small lighting loads where a standard 1 A or higher breaker would not clear a fault before the downstream wiring overheats. The C-curve means it trips magnetically between 5 and 10 times rated current (1.5 to 3 A), so it rides through inrush from small contactor coils or incandescent lamps without nuisance tripping, but still clears a hard short fast enough to protect the 0.75 mm² minimum wire size this breaker accepts. Rated for residential and infrastructure use, it mounts on a standard 18 mm wide DIN-rail slot — one width unit — and can be sealed to prevent tampering. The breaker occupies 18 mm width on a DIN rail, 90 mm tall, 76 mm deep. The screw terminals accept solid or stranded conductors from 0.75 mm² up to 25 mm², with a recommended tightening torque of 2.5 to 3 N·m.","metaTitle":"Siemens 5SL6114-7BB SENTRON MCB, 1P, 0.3 A, C-curve, 6 kA","metaDescription":"Siemens 5SL6114-7BB SENTRON miniature circuit breaker, 1-pole, 0.3 A, C tripping characteristic, 6 kA breaking capacity per EN 60898. Active production, sourced to order. Request a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"1","Width":"18 mm","Height":"90 mm","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"45 °C","Temp Operating Min":"-25 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/448c45311fe75ee70c38c3b99456851d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=411943&mlfb=5SL6114-7BB","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL6114-7BB/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6114-7BB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6114-7BB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}