{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6116-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6116-6","canonicalUrl":"https://aoctrl.com/siemens/5SL6116-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6116-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6116-6, miniature circuit breaker, 1-pole, B characteristic, 16 A, 6 kA per EN 60898, 1 MW unit, IP20.","salesMarkdown":"## Siemens 5SL6116-6 SENTRON MCB — 16 A, B Curve, 1-Pole Rated AC supply voltage is 400 V for multi-phase operation, 250 V single-phase, at 50/60 Hz. Maximum DC rating is 72 V. Mounting position is unrestricted. The sealable design allows padlocking the toggle in the OFF position for lockout/tagout. The 6 kA breaking capacity according to EN 60898 and IEC 60947-2 means this breaker safely interrupts a fault up to 6,000 A without welding its contacts or causing a flashover. For a 16 A final circuit in a domestic or light commercial board with a typical prospective fault level of 3–4 kA, that gives adequate headroom. Energy limitation class 3 means it lets through less energy than class 1 or 2 breakers, reducing stress on downstream wiring. The 10,000 mechanical operating cycles typical service life is standard for an MCB in this class.","metaTitle":"Siemens 5SL6116-6 SENTRON MCB, 1P, B Curve, 16A, 6kA","metaDescription":"Siemens 5SL6116-6 SENTRON miniature circuit breaker, 1-pole, B characteristic, 16 A rated, 6 kA breaking capacity per EN 60898. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL6116-6","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 230/400 V 6kA, 1-pole, B, 16A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","Suitability For Operation":"Residential buildings/infrastructure","at DC rated value maximum":"72 V","Number Of Modular Width Units":"1","Tripping Characteristic Class":"B","supply voltage at AC rated value":"400 V","according to EN 60898 rated value":"6 kA","according to IEC 60947-2 rated value":"6 kA","Type Of Voltage Of The Operating Voltage":"AC","with multi-phase operation at AC maximum":"440 V","Value Range Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"250 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"2 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/448c45311fe75ee70c38c3b99456851d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=208257&mlfb=5SL6116-6"},"ai":{"faq":[{"question":"What is the breaking capacity of the 5SL6116-6?","answer":"The 5SL6116-6 has a 6 kA breaking capacity per both EN 60898 and IEC 60947-2."},{"question":"What is the width of the 5SL6116-6?","answer":"The 5SL6116-6 is 18 mm wide, occupying one modular width unit on DIN rail."},{"question":"Where can I buy the 5SL6116-6?","answer":"The 5SL6116-6 is sourced and quoted to order through independent distribution; availability and current pricing are confirmed at quote time against an RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6116-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6116-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}