{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6116-7YA","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6116-7YA","canonicalUrl":"https://aoctrl.com/siemens/5SL6116-7YA","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6116-7YA","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6116-7YA, miniature circuit breaker, 1-pole, C-curve, 16 A rated current, 6 kA breaking capacity per EN 60898, 400 V AC, 1 modular width unit.","salesMarkdown":"## Siemens SENTRON 5SL6116-7YA — 1-pole C-curve MCB, 16 A, 6 kA The 6 kA breaking capacity per EN 60898 certifies it can safely interrupt a 6 kA prospective short-circuit fault at 230/400 V — the standard for most residential and light commercial distribution boards. At 40 °C ambient, the continuous current rating derates to 0.96 A; at 45 °C it holds 14.88 A, so the 16 A frame is usable in a 40 °C panel only if the load stays well below the derated figure. Snap-on DIN rail mount, any position. Depth 76 mm, width 18 mm (1 MW), height 90 mm. Installation depth 70 mm. IP20 with distribution board cover — the cover is required for finger-safe operation. Sealable terminals allow lockout/tagout. Halogen-free and silicon-free construction.","metaTitle":"Siemens 5SL6116-7YA SENTRON MCB, 1P C-Curve 16A 6kA","metaDescription":"Siemens 5SL6116-7YA SENTRON miniature circuit breaker, 1-pole, C-curve, 16A, 6kA breaking capacity per EN 60898. Sourced to order against an RFQ. Available for quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL6116-7YA","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 230/400 V 6kA, 1-pole, C, 16A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","at AC / rated value":"16 A","protection class IP":"IP20 with distribution board cover","Overvoltage Category":"III","Energy Limitation Class":"3","according to EN 61346-2":"F","at 30 °C / rated value":"16 A","at 40 °C / rated value":"0.96 A","at 45 °C / rated value":"14.88 A","according to IEC 81346-2":"F","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","at DC / rated value / maximum":"72 V","according to EN 60898 / rated value":"6 kA","supply voltage / at AC / rated value":"400 V","Type Of Voltage / Of The Operating Voltage":"AC","with multi-phase operation / at AC / maximum":"400 V","Value Range / Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation / at AC / rated value":"400 V","with single-phase operation / at AC / rated value":"250 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/448c45311fe75ee70c38c3b99456851d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=641135&mlfb=5SL6116-7YA"},"ai":{"faq":[{"question":"Where can I buy 5SL6116-7YA and how do I get a price?","answer":"The 5SL6116-7YA is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will 5SL6116-7YA drop into a panel that was specified around 5SL4106-7CC without rewiring?","answer":"Yes — both share the same 18 mm width, 76 mm depth, 90 mm height, DIN-rail mounting, and 1-pole C-curve form factor. The 5SL6116-7YA carries a 16 A rating versus the 5SL4106-7CC's 6 A, and a 6 kA versus 10 kA breaking capacity per EN 60898. The physical swap is a direct fit; the lower breaking capacity must be verified against the available fault current at the panel."},{"question":"What is 5SL6116-7YA's listed depth (76 mm) on this component line?","answer":"The depth is 76 mm, with an installation depth of 70 mm."},{"question":"What is 5SL6116-7YA's listed width (18 mm) on this component line?","answer":"The width is 18 mm, which corresponds to 1 modular width unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6116-7YA","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6116-7YA when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}