{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6205-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6205-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SL6205-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6205-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6205-7CC, miniature circuit breaker, 2-pole, C characteristic, 0.5 A, 400 V AC, 6 kA breaking capacity per EN 60898, 2 MW units.","salesMarkdown":"The Siemens 5SL6205-7CC is a SENTRON miniature circuit breaker (MCB) with a 2-pole design, C tripping characteristic, and a rated current of 0.5 A at 400 V AC. Its 6 kA breaking capacity is certified per EN 60898, making it suitable for residential and infrastructure branch-circuit protection where short-circuit levels stay within that threshold. At 0.5 A, this is a low-current branch breaker, not a feeder or motor-circuit device. Mounting position is unrestricted — the breaker operates correctly in any orientation. IP20 rating applies only with connected conductors — the terminals are finger-safe when wired, but the breaker itself is not sealed against dust ingress or moisture. Sealable design allows locking in the OFF position for lockout/tagout compliance.","metaTitle":"Siemens 5SL6205-7CC SENTRON MCB, 2-pole C 0.5A 6kA","metaDescription":"Siemens 5SL6205-7CC SENTRON miniature circuit breaker, 2-pole, C-curve, 0.5 A, 400 V AC, 6 kA per EN 60898. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","supply voltage at AC rated value":"400 V","according to EN 60898 rated value":"6 kA","Type Of Voltage Of The Operating Voltage":"AC","with multi-phase operation at AC maximum":"440 V","Value Range Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation at AC rated value":"440 V","vibration resistance according to IEC 60068-2-6":"50 m/s² at 25 to 150 Hz","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"0.9 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/11ee2dc4c1cacb91e4cc204c5ea1e4d7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=395495&mlfb=5SL6205-7CC","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL6205-7CC/alternatives.json"},"ai":{"faq":[{"question":"Will 5SL6205-7CC fit in a panel designed for 5SL4363-7?","answer":"The 5SL6205-7CC is 2 MW wide (36 mm) versus the 5SL4363-7 at 3 MW (54 mm). It will physically snap onto the same DIN rail but occupies one fewer module width. Rewiring is not required if the circuit is 2-pole; the 5SL4363-7 is a 3-pole breaker, so the pole count differs."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6205-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6205-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}